www.evaelektromekanik.com
3
Rated Voltage (kV)
36
Type
eva-36-CR
Main Busbar Rated Current (A)
630 – 1250
Feeder Rated Current
630 – 1250
Rated power frequency withstand voltage
(KV rms)
70
Rated Lightning Impulse Withstand Voltage (kV)
170
Rated Short Circuit Withstand Current (rms)
16kA / 1sec
Rated Peak Withstand Current (kA-Peak)
40
Loss of Service Continuity Class
LSC 2A – PI *
Internal Arc Classification (Cable Connection
and Main Busbar)
IAC – A(FL) 16kA / 1sec
Protection Level (TS 3033 EN 60529)
IP3X
Applied Standard
TS EN / IEC 62271-1, TS EN / IEC 62271-200
Height (mm)
2250
Width (mm)
750
Depth (mm)
1400
1.3 KARAKTERİSTİK ÖZELLİKLER
* LSC 2A - PI DESCRIPTION
LSC 2A
Loss of Service Continuity
2A
When Interfering to the Accessible Part of a Cubicle like the Cable Connection Compartment and
de-energizing it, Neighboring Cubicles May Be Still Energized. In other words, Service Continuity is
Not Restricted.
PI
P: There Are Multiple Sections.
I: These Sections Are Separated From Each Other By Insulating Material.