In accordance with the single line diagram of the facility, combine the square-shaped holes of the cubicles side by
side using M8x20 bolts.
1. According to the “3.3- CUBICLE’S PLACEMENT” article stated
above, remove the upper cover plate of the connected
cubicles.
2. Connect the main busbars shipped with the cubicles to the
main bus terminal using field regulators and tighten the bolts
with 50Nm torque.
3.
Wipe the insulators and solid insulation materials with a dry
clean cloth.
4. Assemble the upper cover plate.
IMPORTANT WARNING:
If the surface
on which the cubicles will be mounted
is not flat, the cubicles’ covers may not
be fitted properly and also problems
may be caused in the main busbar
connection.
3.5 -MAIN BUSBARS CONNECTION
MAIN BUSBAR TYPES:
MAIN BUSBAR CURRENT AND THICKNESS
Busbar Material
630 A
1250 A
Copper (Cu)
40x5 mm
2
60x10 mm
2
Aluminum (Al)
40x10 mm
2
*
IMPORTANT WARNING:
Do not step or walk on the
main busbars, disconnectors and load break switches.
Содержание eva-36-CR