6
•
Place the MMMH Type cubicle on a channel inside
the building in accordance with the dimensions
indicated in the right picture.
•
•
A 5cm gap should be left between the placed
cubicles on the right or the left side inside the
building and the wall.
•
•
Close the channel gaps.
•
•
Do not go below the dimensions indicated in the
right picture.
3.3.1 Placement inside the Building:
3.3 - CUBICLE’S PLACEMENT
•
Base holes that enable the cubicles to be fixed to the ground are provided as shown in the below picture.
•
Fix the cubicles to the ground by using M10 steel peg or iron dowel.
• The dispatched cubicles should
be placed on the side and
according to the illustrated
figure.
•
Do not go below the provided
dimensions.
• The building dimensions can be
determined accordingly.
• The gaps between the cubicles
from one side and the ceiling
and the back wall from the other
side should be at least 300mm
and 100mm respectively.
IMPORTANT WARNING:
Содержание eva-36-CR