1-5
TE200S User manual
IDENTIFYING THE SOLID STATE RELAYS
TECHNICAL SPECIFICATION
The TE200S series of SSRs is intended for two-phase control of an industrial
three-phase load.
Power
Nominal current (per phase)
16A, 25A, 40A, 50A or 63A (at 45°C)
Line-to-line voltage
200Vac to 500Vac (±10%) depending on the
voltage code
Supply frequency
50Hz and 60Hz (±2Hz) automatic selection
Dissipated power
1.3W (approx.) per amp, per phase
Insulation (1 min test)
Between power and earth:
In series 2000Vac, 50Hz
Between power and control:
In series and 3600Vac, 50Hz.
Cooling
Natural convection for 16A to 50A rated units Permanent
fan-cooling for 63A rated unit
Fan power supply
115Vac or 230Vac (selected in order code)
Load
Resistive three-phase load with a low temperature
coefficient
Short-wave infrared elements (except for 63A rated unit)
Supply phases
Wiring independent of the phase rotation
Load configuration
3-wire: Closed delta or star without neutral
Fuses
External (order separately) see chapter 5
CE Marking
Electrical safety
TE200S SSRs carry the CE mark in compliance with the
essential requirements of the European Low Voltage
Directive 73/23/EEC (amended by the Directive
93/68/EEC)
Electromagnetic compatibility
Immunity and Emissions
TE200S products comply with Electromagnetic
Compatibility test standards (see page iv).
Содержание TE200S
Страница 40: ......