5-3
TE200S User manual
MAINTENANCE
To protect the thyristors in the TE200S, depending on the wiring configuration the following
combinations may be used:
• Two ‘single-phase fuse and fuseholder’ assemblies installed in the controlled phases or
• One ‘three-phase fuse and fuseholder’ assembly installed between the TE200S SSR and
the cable protection and mains circuit breaker; in the direct phase it is possible to install a
solid link instead of a fuse.
References for the ‘fuse and fuseholder’ assemblies and for spare fuses are given in the
following tables.
Nominal Spare
fuse
Code
current
References:
Fuse+fuseholder
Dimensions
TE200S Fuse
Eurotherm
Ferraz
Assembly
(mm)
16A
20A
CH 260024
K330013
FU1038/16A/00
81 x 17.5 x 68
25A
30A
CH 260034
M330015
FU1038/25A/00
81 x 17.5 x 68
40A
50A
CH 330054
B093910
FU1451/40A/00
95 x 26 x 86
50A
63A
CS 173087U063
T094823
FU2258/50A/00
140 x 35 x 90
63A
80A
CS 173246U080
W076310
FU2760/63A/00
150 x 38 x 107
Table 5-1 Recommended high-speed fuses for thyristor protection
Single-phase fuseholders.
Nominal Spare
fuse
Code
current
References:
Fuse+fuseholder
Dimensions
TE200S Fuse
Eurotherm
Ferraz
Assembly
(mm)
16A
20A
CH 260024
K330013
FU3038/16A/00
81 x 52.5 x 68
25A
30A
CH 260034
M330015
FU3038/25A/00
81 x 52.5 x 68
40A
50A
CH 330054
B093910
FU3451/40A/00
95 x 79 x 86
50A
63A
CS 173087U063
T094823
FU3258/50A/00
140 x 108 x 90
63A
80A
CS 173246U080
W076310
FU3760/63A/00
150 x 114 x 107
Table 5-2 Recommended high-speed fuses for thyristor protection