Manual EKS Ethernet TCP/IP
Page 30/38
Subject to technical modifications
2547185-01-10/22
2. Click
Configuration
.
The
Configuration
screen for the EKS web interface is now displayed.
3. Enter the desired IP address and the subnet mask. If the network has a gateway, also enter this information.
4. Click the
Send
button.
The following message is displayed:
The settings were saved, to apply settings please switch power off/on…
5. Interrupt the power supply and connect the device again in order to adopt the settings.
Information!
With the modular interface adapter, the RESET button on the front can be used to disconnect the power
supply and restart the device.
The areas of the web interface described in the following are used for the extended analysis of the connection
from the EKS to the software application.
In the
Active Connection Data
area, the number of currently active connections is shown including the
parameters for the connection to the application. Here only one connection is allowed to be active. If there are
more than three connections, the EKS outputs the status number 61
hex
(see chapter 8.5) and the
communication is interrupted. The connection to the web interface is not indicated here. The active connections
are deleted when the device is shut down.
In the
Connection Data History
area, the total number of all boot processes is indicated after
Current Boot
Count
. The last 20 EKS connections to the application are also listed chronologically with the connection
parameters. These entries are not deleted while resetting to the default IP address (see chapter 6.1.1.1).