Manual EKS Ethernet TCP/IP
2547185-01-10/22
Subject to technical modifications
Page 13/38
4.4 Technical data for compact version
Attention!
All the electrical connections must either be isolated from the mains supply by a safety transformer
according to EN IEC 61558-2-6 with limited output voltage in the event of a fault, or by other equivalent
isolation measures.
General parameters
Value
Unit
min.
typ.
max.
Housing
Plastic (PA 6 GF30, gray)
Degree of protection
IP65/IP67 in installed state
Ambient temperature at UB = DC 24 V
0
+ 55
°C
Mounting cut-out acc. to DIN IEC 61554
33 x 68
mm
Power supply connection
Plug-in connection terminal, 3-pin, with screw terminal
(tightening torque 0.22 Nm),
conductor cross-section 0.14 ... 1.5 mm²
Operating voltage U
B
(regulated, residual ripple < 5 %)
20
24
28
DC V
Current consumption I
B
150
mA
Interface, data transfer
Interface to the control system
Industrial Ethernet (IEEE 802.3)
Transfer protocol
TCP/IP
Data transfer rate (full duplex)
10/100
Mbit/s
Connection for Ethernet interface
1 x RJ45 socket
Data line
2 x 2 twisted-pair copper cables, screened; min. category 5
Cable length
100
m
LED indicator
Green: “Ready” (in operation)
Yellow: “Electronic-Key active” *
Red: “Fault”
Version
FSA
(For Safety Applications) – parameters for floating semiconductor switching contacts LA and LB
Switching contact connection
Plug-in connection terminal, 4-pin, with screw terminal
(tightening torque 0.22 Nm),
conductor cross-section 0.14 ... 1.5 mm²
Power supply U for load (LA, LB)
24
30
V
Switching current (with overload protection)
1
10
50
mA
Output voltage U
A
(LA, LB) in switched state
U x 0.9
U
V
Resistance in switched state
35
ohms
Max. capacitive load
1
µF
Utilization category acc. to AC-12
EN IEC 60947-5-2 AC-15
DC-12
DC-13
50 mA / 24 V
Difference time of the outputs** (LB first)
200
ms
Reliability values acc. to EN ISO 13849-1 (
FSA
version only)
Category (with downstream safe evaluation)
3
MTTF
D
Evaluation of data channel and one
switching contact LA
416
years
Evaluation of data channel and both
switching contacts LA and LB
803
years
DC
92
%
* The LED illuminates yellow if there is a functional Electronic-Key in the Electronic-Key adapter.
** If the Ethernet interface is accessed during placement or removal of the Electronic-Key,
the difference time can be more than 200 ms.