RDT-07-0122
33
®
NORD
fire
|
FDMQ
Images are for illustrative purposes
We reserve the right to make changes
48
*
Kogu perimeetri ulatuses
*
Kogu perimeetri ulatuses
80
≤ 75*
≥ 100
≤ 75*
≥ 20*
80
≥ 100
EIS 60
Installation opening has to
be reinforced by steel U-pro-
file. Profile is fixed by screws
≥3,5 mm with corre-sponding
length. Distance between
screws ≤200 mm.
5.5 Installation outside gypsum wall construction
Fig. 35 Outside gypsum wall construction- mineral wool- mortar or gypsum
EIS 60
Position:
1 Fire damper
2 Gypsum plate
3 Mineral wool (type depending on the type of construction)
4 Mortar or gypsum
5 Stone wool with wired mat on one side, density 66 kg/m³
6 Duct
Used materials - example:**
5 Isover Ultimate Protect SLAB 4.0, th. 80 mm ALU1
** The materials for stuffing box, fire protection mastic, lining and insulation materials can be replaced by
another approved fire sealing system with equivalent properties. The maximum distance of the fire damper
from the structure is not limited and according to EN 15882-2, the required number of suspensions acc. to
EN 1366-1:2014 must be used.
The duct at the point of penetration can be anchored to the fire wall construction!
Shown schemes of incorporation and damper are illustrative only!
* Around the perimeter