RDT-07-0122
19
®
NORD
fire
|
FDMQ
Images are for illustrative purposes
We reserve the right to make changes
30
≤ 75*
≥ 100
≥ 20
≤ 75
≥ 100
5.2 Installation in solid wall construction
Fig. 20 Solid wall construction- mortar or gypsum
EIS 120
EIS 90
Position:
1 Fire damper
2 Solid wall construction
3 Mortar or gypsum
4 Duct
Shown schemes of incorporation and damper are illustrative only!
Fig. 21 Solid wall construction- fire protection foam with stucco plaster
EIS 60
EIS 45
EIS 30
Position:
1 Fire damper
2 Solid wall construction
3 Fire protection foam
4 Stucco plaster
5 Duct
Used materials - example:*
3 HILTI CFS-F FX - EIS 60
PROMAFOAM-C - EIS 45
SOUDAL, Soudafoam FR-B1 - EIS 30
DenBraven, Fire protection foam - EIS 30
30
≤ 75*
≥ 100
≥ 20
≤ 75
≥ 100
The damper must be anchored to the fire wall
construction!
Shown schemes of incorporation and damper are
illustrative only!
* Around the perimeter