32
EN
•
Voltage sensing
Dec. Address
Word
count
Description
Unit
10192
1
Source 1 L1-N voltage value
(V)
10193
1
Source 1 L2-N voltage value
(V)
10194
1
Source 1 L3-N voltage value
(V)
10195
1
Source 1 L-N average voltage
(V)
10196
1
Source 1 L1
–L2 voltage value
(V)
10197
1
Source 1 L2
–L3 voltage value
(V)
10198
1
Source 1 L3
–L1 voltage value
(V)
10199
1
Source 1 L-L average voltage
(V)
10204
1
Source 1 frequency
(0.1 Hz)
10205
1
Source 2 L1-N voltage value
(V)
10206
1
Source 2 L2-N voltage value
(V)
10207
1
Source 2 L3-N voltage value
(V)
10208
1
Source 2 L-N average voltage
(V)
10209
1
Source 2 L1
–L2 voltage value
(V)
10210
1
Source 2 L2
–L3 voltage value
(V)
10211
1
Source 2 L3
–L1 voltage value
(V)
10212
1
Source 2 L-L average voltage
(V)
10217
1
Source 2 frequency
(0.1 Hz)
•
Communication parameters
Dec. Address
Word
count
Description
Unit
40017
1
C25 communication node address:
1-247
40018
1
Baud rate :
2
– 2400
3
– 4800
4
– 9600
5
– 19200
6
– 38400
40019
1
Serial Data format : 1-5
1- 8N
2
– 80
3
– 8E
4
– 70
5
– 7E
40020
1
Stop bit:
1
– 2
As standard the baud rate is set to 38400, parity bit to 1, Modbus address 3 these parameters can be changed using the write
function 10.
Once the configuration is done, write data 1 at address Dec. 40565. After changing the parameters the product buzzer will
sound twice and the Com LED will stay on.
To reset to default parameters press the RES button for 30 seconds, the product will reboot and the standard communication
settings will be set.
Содержание 004661922
Страница 1: ...EN INSTRUCTION MANUAL ATSC25 ATS Controller www eti eu support...
Страница 25: ...EN 25 11 2 Connection diagrams 11 2 1Connections with MLBS 4P 63 125...
Страница 26: ...26 EN 11 2 2Connections with standard Contactors CEM and CES...
Страница 27: ...EN 27 11 2 3Connections with MCCBs EB2 and MO2...
Страница 34: ......