EN
15
•
6.3 Terminal denomination, description and characteristics
Denomination
Terminal
Description
Characteristics
Recom-
mended
Cable section
Tightening
torque /
screw type
Control signal
outputs (orders to
RTSE)
14
Position II order
AC1
– General use – Ie: 5A , Ue: 250
V.a.c DC1
– General use – Ie: 5A , Ue:
30 V.d.c AC15 - Ie: 3A, Ue: 120 V.a.c
AC15 - Ie: 1.5A, Ue: 240 V.a.c
DC13 - Ie: 0.22A, Ue: 125
V.d.c DC13 - le: 0.11A, Ue:
250 V.d.c
1-
2.5mm²
0.58 Nm
15
Position I order
16
Position 0 order
17
Common point for
position output
RS485
35
NC
– Not connected
RS485 Isolated bus
36
Negative electrode
37
Positive electrode
Genset output
51
Common point
52
Closed to start the Genset
(closed when controller is
powered off)
AC1
– General use – Ie: 3A , Ue: 250
V.a.c DC1
– General use – Ie: 3A , Ue:
30 V.d.c AC15 - Ie 54/51: 3A 52/51: 1.5A
Ue: 120 V.a.c
AC15 - Ie 54/51: 1.5A 52/51: 0.75A Ue: 240
V.a.c DC13 - Ie 54/51: 0.22A 52/51: 0.22 A 125
V.d.c DC13 - Ie 54/51: 0.11A 52/51: 0.11 A 250
V.d.c
54
Open to start the genset
Controller inhibit
input
63A
Controller is inhibited when
this contact is open
Do not use external voltage - Power from common
point
0.5-
1.5mm²
0.2 Nm/ M2
64A
Return of information
from RTSE (Position
inputs)
70
Common point for
position inputs
Do not use external voltage - Power from common
point
71
Position I RTSE
72
Position II RTSE
73
Position 0 RTSE
Fire input
F1
Negative electrode of the 24
V.d.c
12-24 V.d.c
F2
Positive electrode of the
24
V.d.c
Optional Aux
supply
24V.d.c
81
Negative electrode of the 24
V.d.c
10-30 V.d.c (Auxiliary supply for controller, does not
supply RTSE)
1-
2.5mm²
0.58 Nm / M3
82
Positive electrode of the
24
V.d.c
Source 1 and 2
voltage
inputs
103
Source 1 N
Sensing range:
90-520 V.a.c (ph-ph)
50-300 V.a.c (ph-n)
45-65 Hz
Supply:
184-300 V.a.c* (ph-n)
45-65 Hz
Max consumption 10 W
*200-300 V.a.c in maintained mode
104
Source 1 L1
105
Source 1 L2
106
Source 1 L3
203
Source 2 N
204
Source 2 L1
205
Source 2 L2
206
Source 2 L3
DPS output
(RTSE power
supply)
301
Phase output
AC
– General use – Ie: 6A , Ue: 250
V.a.c DC
– General use – Ie: 6A , Ue:
30 V.d.c AC15 - Ie: 3A, Ue: 120 V.a.c
AC15 - Ie: 1.5A, Ue: 240 V.a.c
DC13 - Ie: 0.22A, Ue: 125
V.d.c DC13 - le: 0.11A ,Ue:
250 V.d.c
302
Neutral output
*LiYCY sheilded twisted pair
NOTE 1: Use 7mm as stripping length for the controller terminals
NOTE 2: Use 90°C copper wire for installations with ambient temperature from 35-60°C.
When the ambient temperature is
above 60°C, Use 105°C copper wire.
Содержание 004661922
Страница 1: ...EN INSTRUCTION MANUAL ATSC25 ATS Controller www eti eu support...
Страница 25: ...EN 25 11 2 Connection diagrams 11 2 1Connections with MLBS 4P 63 125...
Страница 26: ...26 EN 11 2 2Connections with standard Contactors CEM and CES...
Страница 27: ...EN 27 11 2 3Connections with MCCBs EB2 and MO2...
Страница 34: ......