7. ATSC25 OPERATING MODES
The ATSC25 has 3 distinct working modes, the working modes are selected using the HMI button or by using the 63A/64A
input.
The 3 working modes are working as described below:
• Auto mode
In this mode the controller will automatically give orders to the RTSE connected to switch to the correct position according to
the settings selected.
In this mode, the manual order buttons
,
,
are disabled.
This mode is activated when the LED 7 is ON (fixed). To access this Mode make sure that you are in manual mode (the LED
7 is OFF and that the fault LED (12) or the TEST LED (8) are not activated) and then press the button for 3 seconds, the
LED 7 should then turn ON.
• Manual mode
In this mode the manual orders buttons
,
,
enable manual orders to switch respectively to position I , 0 or II.
This mode is activated when the LED 7 is OFF and the LED 12 is OFF and that the fault LED (12) or the TEST LED (8)
are not activated. To switch from AUTO mode to manual mode, press the button
for 3 seconds.
• Inhibit mode
In this mode both the Automatic transfer and manual orders will be blocked. This mode is activated when the input 63A/64A is
OPEN.
In this mode the fault LED (12) will be blinking, and AUTO LED will be OFF. To leave the inhibit mode close the 63A/64A
input, the controller will return to the last working mode (Automatic or Manual).
Содержание 004661922
Страница 1: ...EN INSTRUCTION MANUAL ATSC25 ATS Controller www eti eu support...
Страница 25: ...EN 25 11 2 Connection diagrams 11 2 1Connections with MLBS 4P 63 125...
Страница 26: ...26 EN 11 2 2Connections with standard Contactors CEM and CES...
Страница 27: ...EN 27 11 2 3Connections with MCCBs EB2 and MO2...
Страница 34: ......