7.3  Fixed outputs 

 

 

10.3.1.  Control signal outputs

 

 

Control  signal  outputs  are  the  output  orders  (dry  contact)  to  the  RTSE;  the  
ATSC25 includes 3 signal outputs and a common (point powered by the user) 
(Terminals 17 to 14). These outputs are rated for 250 Vac, 50/60 Hz 5A general 
use , and 30 V.d.c 5A general use.

 

 

 

These outputs function as described below:

 

When order 0 is given through the Automatism in automatic mode or manually using the button 

 the contact between 

17 and 16 will be closed.

 

When order I is given through the Automatism in automatic mode or manually using the button 

 the contact between 

17 and 14 will be closed.

 

When order II is given through the Automatism in automatic mode or manually using the button 

 the contact between 

17 and 15 will be closed.

 

 

 

These outputs can be impulse or maintained depending on the setting on DIP switch 3 Order Mod.

 

In maintained mode when an order is sent it will be maintained until a different order is sent.

 

In impulse mode orders are sent for maximum 5s and are stopped when either 5s has expired or the controller received feedback 
that  the  RTSE  has  reached  the  requested  position.  If  5s  expire  and  the  RTSE  has  not  reached  the  requested  position  the 
controller will consider this as a fault and will inhibit the automatism until the fault is cleared.

 

 
 
 

10.3.2.  Genset start output

 

 

Genset start outputs are the output orders (dry contact), the contact between 51 and 54 
will open & the contact between 51 and 52 will close when the signal to start the genset 
should be sent (during a test on load or when source 1 is lost). These outputs are rated for 
250 V.a.c, 50/60 Hz 5A general use for NO contact and 3A general use for NC  contact, 
and 30 V.d.c 5A general use for the contact between 51-54 and 3A general use for the 
contact 51-52.

 

 

Control

 

51/54

 

51/52

 

Generator Start

 

Contact open

 

Contact closed

 

Generator Stop

 

Contact closed

 

Contact open

 

 

When the switch returns in position I the Cooldown timer will start counting (Default value 180s) during the cooldown timer, the 
contacts will maintain the generator start signals.

 

 

If the 24 V.d.c auxiliary power supply is not used the timer 1FT will not count and the

 

order to start the generator will be sent immediately when source 1 is lost.

 

CAUTION

 

Содержание 004661922

Страница 1: ...EN INSTRUCTION MANUAL ATSC25 ATS Controller www eti eu support...

Страница 2: ...instruction manual must be made accessible so as to be easily available to anyone who may need to read it in relation with the ATSC25 The ATSC25 meets the European Directives governing this type of p...

Страница 3: ...004 30 UE LVD Low voltage directive 2014 35 UE EMC according to IEC EN 60947 6 1 and GB T 14048 11 including annex C IEC EN 61326 1 standard Vibration according to IEC 60068 2 6 GB T 2324 10 Shock tes...

Страница 4: ...e with PC and CC type RTSE ATSC25 ATS Controller Ensures Monitoring of the availability of a Normal and Alternate source Supply to the controller and switch from the Normal or Alternate source Transfe...

Страница 5: ...EN 5 4 GENERAL OVERVIEW 4 1 Product identification 1 AUTO Manual selector 2 Controller state LED 3 Remote position order selector 4 ATSE Synoptic 5 Test function selector 6 DIP switch programing...

Страница 6: ...2 is present and available within threshold limits green blinking when source 2 is present but outside of threshold limits off when under 50VAC 7 Auto LED indication Green fixed when in automatic blin...

Страница 7: ...according to IEC 61010 1 95 humidity without condensation 50 C according to GB14 11 Annex Q EMC IEC EN 60947 6 1 and GB T 14048 11 including annex C standards IEC EN 61326 1 Altitude Up to 2000m Stora...

Страница 8: ...tion class Pollution class II Other compliances and marking 4 4 CONTENT OF PACKAGING The C25 packaging includes 1 C25 controller 1 C25 quickstart guide All connector Door mounting clips All other prod...

Страница 9: ...mm 5 5 2 Mounting Door mounting Door cut out of 93 0 8 x138 1 mm door thickness 1 5 3mm Remove all connectors and clip before inserting the controller in the cut out then fix the controller in place u...

Страница 10: ...mounting Install on IEC 60715 Standard Din RAIL When mounting make sure both clips are pushed up then clip on the DIN Rail To remove from the DIN Rail drag the two mounting clips down before removing...

Страница 11: ...In these networks the phase must be connected to the L1 input terminal 104 for source 1 and 204 for source 2 3P N The ATSC25 is suitable for three phase with neutral networks for with voltages within...

Страница 12: ...2 Connections TOP In 3 phases with Neutral balanced networks there is a risk that the loss of neutral will not be detected To limit this risk the Dip switch 4 Hysteresis can be switched to position A...

Страница 13: ...input 2 24 V d c fire input 3 Enable control when closed disable control when open 4 RS485 connections 5 Genset Start relay 6 RTSE position control outputs 7 Source 1 and 2 voltage inputs 8 24 V d c A...

Страница 14: ...14 EN 6 2 Connection diagrams with MLBS 3P 4P 250 630A For additional connection diagrams MLBS 4P 63 125 Contactors etc see ANNEX I...

Страница 15: ...1 5mm 0 2 Nm M2 64A Return of information from RTSE Position inputs 70 Common point for position inputs Donotuseexternalvoltage Powerfromcommon point 71 Position I RTSE 72 Position II RTSE 73 Position...

Страница 16: ...12 or the TEST LED 8 are not activated and then press the button for 3 seconds the LED 7 should then turn ON Manual mode In this mode the manual orders buttons enable manual orders to switch respecti...

Страница 17: ...at the phase rotation is identical on both sources If the sources have different phase rotations the source available LED will be blinking on both sources 7 2 1 Frequency within set limits The ATSC25...

Страница 18: ...d when either 5s has expired or the controller received feedback that the RTSE has reached the requested position If 5s expire and the RTSE has not reached the requested position the controller will c...

Страница 19: ...r will be on to clear the fault expected position input should be closed and the user must press the AUTO button 73 70 must be closed when the RTSE is in position 0 72 70 must be closed when the RTSE...

Страница 20: ...e configuration will remain the same DIP Switch 1 Network A Three phase network B Single phase network 2 Prio Set A Prioritty source 1 B No priority 3 Order Mod A Control mode impulse logic B Control...

Страница 21: ...roduct in a full operating cycle I 0 II 0 I Auto and Manual as well as tightening the door mounting clips and testing the LED s with the lamp test button when applicable In case of upstream protection...

Страница 22: ...rotation Alarm LED is blinking Verify that the input 63 64 is closed Verify that there has not been a problem during a transfer order and validate fault with the AUTO button Verify that the DIP switch...

Страница 23: ...when source 2 is present and available within threshold limits green blinking when source 2 is present but outside of threshold limits off when under 50VAC 7 Auto LED indication Green fixed when in a...

Страница 24: ...ilability Source 2 present but not available for following possible reason Source undervoltage under frequency Source overvoltage over frequency Phase rotation order of source 1 2 are different Source...

Страница 25: ...EN 25 11 2 Connection diagrams 11 2 1Connections with MLBS 4P 63 125...

Страница 26: ...26 EN 11 2 2Connections with standard Contactors CEM and CES...

Страница 27: ...EN 27 11 2 3Connections with MCCBs EB2 and MO2...

Страница 28: ...lt value for nominal voltage is 230 V a c and the default value for nominal frequency is 50Hz To reboot the product press the button for 30s this will restart the product and take into account any cha...

Страница 29: ...n source 1 is available the controller will give the order to switch to position I 11 6 2 No prio if both sources are available the controller will give the order to remain in the current position 12...

Страница 30: ...30 EN 13 ATSC25 Operatingsequence Controller operating sequence with source 1 priority DPS Output operating sequence...

Страница 31: ...F 1 ON 10011 1 Fire Input state F1 F2 0 OFF 1 ON 10012 1 CTRL inhibit 63A 64A 0 Inhibit 1 Automatic 10022 1 Genset control output 51 52 54 0 Genset start order OFF 0 Genset start order ON 10023 1 Cont...

Страница 32: ...L2 L3 voltage value V 10211 1 Source 2 L3 L1 voltage value V 10212 1 Source 2 L L average voltage V 10217 1 Source 2 frequency 0 1 Hz Communication parameters Dec Address Word count Description Unit 4...

Страница 33: ...ount in AUTO mode 0 60 000 10128 2 Position II operation count in AUTO mode 0 60 000 10130 2 Position I operation count in Manual mode 0 60 000 10132 2 Position II operation count in Manual mode 0 60...

Страница 34: ......

Страница 35: ...foretage indgreb under drift under bestemte forhold med s rlige midler kvalifikationer og godkendelser Produktet m ikke repareres af brugeren Kontakt ETI hvis der er sp rgsm l vedr rende anvendelsen a...

Страница 36: ...c AC15 Ie 54 51 1 5A 52 51 0 75A Ue 240 V a c DC13 Ie 54 51 0 22A 52 51 0 22 A 125 V d c DC13 Ie 54 51 0 11A 52 51 0 11 A 250 V d c 54 Open to start the genset Controller inhibit input 63A Controller...

Отзывы: