Installation

13

Suspension Mounting

• Standard kits are available for suspension mounting with 1/16 in (1.6 mm) aircraft cables. See 

page 38

• When mounting with threaded rod, the recommended threaded rod size is 3/8 in (9.52 mm).
• Additional track accessories are required for suspension mounting. See 

DataTrack Mounting 

Accessories

 on 

page 37

 for more details.

• Be sure to consider track stability in suspension mounting applications. Vibrations caused by 

HVAC operation and other building systems could impact the function of the DataTrack system.

Note:

All hardware for attaching wire rope or threaded rod to appropriate building 

structure is the responsibility of the installing contractor.

Содержание EUTRAC

Страница 1: ...ended Load Capacity 8 DMX Data Path 8 Chapter 2 Installation 11 Cutting Track 11 Installation Methods 12 Surface Mounting 12 Suspension Mounting 13 Installing End Feeds 14 Installing Mid Feeds 17 Inst...

Страница 2: ...k System Planning and Installation Manual Appendix A Parts and Accessories 28 Two circuit DataTrack Accessories 28 DataTrack Mounting Accessories 37 Current Limiters 40 Appendix B Reconfiguring DMX Da...

Страница 3: ...ocated directly at the track Up to 22 pounds of weight per foot when properly supported Two year warranty White black powder coated and silver anodized finishes 4 ft 8 ft and 12 ft 1 21 m 2 43 m and 3...

Страница 4: ...ion that is supplemental to the main text CAUTION A Caution statement indicates situations where there may be undefined or unwanted consequences of an action potential for data loss or an equipment pr...

Страница 5: ...ther than lighting track fixtures on the track WARNING Do not attempt to connect power tools extension cords appliances or similar devices to the track CAUTION This document describes 120V DataTrack i...

Страница 6: ...ng for support please try to have the following information available Product model Other components in your system luminaires connected control source etc Americas United Kingdom ETC Inc ETC Ltd Tech...

Страница 7: ...bus portion of the track This is important to keep in mind when purchasing couplers ground left versus ground right ground inside versus ground outside All product references to ground orientation al...

Страница 8: ...e coupler must mate with the data connection of the track This is important to keep in mind when choosing couplers ground left versus ground right ground inside versus ground outside Note These figure...

Страница 9: ...ve the ground connectors on the left side of the T instead of the right as shown they will not align with the connectors in the X couplers T coupler ground inside left Ground Feed Path L coupler groun...

Страница 10: ...ur local ETC representative For more information on DMX visit the ETC website http www etcconnect com Support Articles DMX 512 Info aspx Distance between mounting points Maximum load per foot 36 in 91...

Страница 11: ...upler ground inside L coupler ground inside L coupler ground inside Key DMX IN DMX dead zone or second DMX input required DMX TERM L coupler ground inside L coupler ground inside L coupler ground insi...

Страница 12: ...See Reconfiguring DMX Data Lines on page 43 for more information T2 D2 D1 D3 T3 T1 T coupler ground inside right T coupler ground inside right T coupler ground inside right T coupler ground inside rig...

Страница 13: ...rack The minimum distance that the bus bar can be cut back from the edge of the track profile is 0 08 in 2 mm The bus bar does not have to be moved out of the track profile Use a file to remove burrs...

Страница 14: ...ack by a cable or threaded rod Be sure to follow the installation instructions supplied with each component when installing the track system Surface Mounting Pre punched holes are positioned every 8 i...

Страница 15: ...ccessories are required for suspension mounting See DataTrack Mounting Accessories on page 37 for more details Be sure to consider track stability in suspension mounting applications Vibrations caused...

Страница 16: ...e end feeds For top feed a Remove the cover screw b Remove the cover c Remove the plug For end feed a Remove the cover screw b Remove the cover c Remove the plug d Install the wire guide to the end fe...

Страница 17: ...etainer down d Connect the feed wires to the terminals as illustrated and secure the screws Figure 5 Connect the end feed L1 L1 L2 L2 N2 N2 N1 N1 a b d c Electrical connection for two 20A circuits at...

Страница 18: ...l the wire retainer b Connect data line wires to screws as illustrated to track c Install the cover d Install the cover screw When using DataTrack with DMX it may be necessary to use separate feed con...

Страница 19: ...anopy 3 Feed the power line wires through the track Concurrently mount the track by referring to the instructions provided with the track Figure 9 Feed power lines and mount track Drill hole on top of...

Страница 20: ...and remove the cover Figure 10 Press in the catch and remove cover 5 Insert the mid feed into the track at the prepared position Figure 11 Mounting example 6 Using the enclosed hexagonal head wrench t...

Страница 21: ...cted as indicated in Figure 13 and Figure 14 Circuits 1 and 2 can be wired as required Figure 13 Wiring Figure 14 Dismantling and insulation strip lengths Figure 15 Dismantling and insulation strip le...

Страница 22: ...b Reposition the cover c Click into place Figure 16 Secure the cover Figure 17 Wiring a b C click Standard DMX control systems may only be used if they fulfill SELV Safety Extra Low Voltage requireme...

Страница 23: ...er 3 Track Feed Connector 2 10 Track Feed Connector 1 4 Round Knockout 11 Ground Tab 5 Line Terminal Hot 12 Line Terminal Hot 6 Current Limiting Circuit Breaker sold separately 13 Load Terminal 7 Load...

Страница 24: ...plate on ceiling to determine the mounting location of the feed connector 3 Make a hole in the ceiling for the electrical connector in a position that coincides with one of the round knockouts 4 Remo...

Страница 25: ...of feed connector Clamp wire using screw See Figure 18 Figure 18 End feed wiring 3 Strip Hot 1 supply wire and connect to a 0 25 in 6 35 mm female quick disconnect not supplied Push onto the Line tap...

Страница 26: ...it breaker 5 Connect load from current limiting circuit breaker to feed connector terminal L1 using provided wire 6 Measure and strip a new wire not provided and connect L1 terminal Feed Connector 1 t...

Страница 27: ...raight runs Check all connections of track If connections check is good check components for proper earth inside outside If parts are incorrect change parts for the correct current flow Check live end...

Страница 28: ...k again for data Loss of data on suspended track cable or pendant Check that the joined track sections have been joined by pendant clips Track sections must be joined by pendant clip Use 2 in 5 08 cm...

Страница 29: ...ew and then the other Finish securing screws with screwdriver Make sure wires are not interfering with cover Remove cover Tuck any loose wires out of the way when closing the cover Never interfere wit...

Страница 30: ...2 81 in 71 5 mm 1 37 in 34 9 mm 1 40 in 35 6 mm 0 42 in 10 6 mm Feeds power and or data into the DataTrack system Mounts to the end of a linear section of DataTrack Top feed or end feed Ground Color...

Страница 31: ...ed only Splices two pieces of DataTrack in line Supports power and or data feed Top feed only Color Model Number Black EDTRMF White EDTRMF 1 Silver EDTRMF 5 4 57 in 116 0 mm 1 36 in 34 5 mm 0 29 in 7...

Страница 32: ...upports power and or data feed Top feed only Either ground outside or ground inside Ground Color Model Number Inside Black EDTRLC GI White EDTRLC GI 1 Silver EDTRLC GI 5 Outside Black EDTRLC GO White...

Страница 33: ...lor Model Number Inside Right Black EDTRTC GIR White EDTRTC GIR 1 Silver EDTRTC GIR 5 Inside Left Black EDTRTC GIL White EDTRTC GIL 1 Silver EDTRTC GIL 5 Outside Right Black EDTRTC GOR White EDTRTC GO...

Страница 34: ...DataTrack at a 90 angle Supports power and or data feed Top feed only Data can be routed to either pair of interior corners field configurable Color Model Number Black EDTRXC White EDTRXC 1 Silver EDT...

Страница 35: ...splicing two pieces of DataTrack in line Requires 4 in 10 16 cm pendant clip to stabilize joint see Four inch Pendant Clip on page 37 Color Model Number Black EDTRFC White EDTRFC 1 Silver EDTRFC 5 2 8...

Страница 36: ...ng surface created for feed wires from junction boxes Color Model Number Black EDTREC White EDTREC 1 Silver EDTREC 5 0 53 in 13 5 mm 0 11 in 2 8 mm 0 49 in 12 3 mm 1 43 in 36 2 mm 1 26 in 32 0 mm Colo...

Страница 37: ...1 27 cm mounting bolt Mechanical rotation stop with spring prevents fixtures from falling when adapter is unfastened Maximum load 22 lb 9 97 kg Color Model Number Black EDTRMCC White EDTRMCC 1 Silver...

Страница 38: ...quired per data feed positioned at the end of the DMX data run Multiple data feeds and terminations may be required in a single DataTrack system Color Model Number Black EDTRDMXT White EDTRDMXT 1 Silv...

Страница 39: ...eaded rod standard mounting kits with 24 in or 36 in 0 60 m or 0 91 m lengths are available Required for joints of pendant mounted tracks Color Model Number Black EDTR2PC White EDTR2PC 1 Silver EDTR2P...

Страница 40: ...1 16 in 1 6 mm aircraft cable Canopy Cable gripper Coupler The diameter of the hole for running cable through the support feed canopy kit is 7 8 in 22 22 mm For attaching top of aircraft cable to buil...

Страница 41: ...ies 39 T bar Mounting Clip For use with 15 16 in 23 81 mm T grid system Support independent of ceiling Kit from ETC includes mounting nut Color Model Number White EDTRTB 0 75 in 19 1 mm 3 51 in 89 1 m...

Страница 42: ...ircuit breakers must be ordered separately see Circuit Breaker on page 42 for options Title 24 Compliant Ground Color Model Number Right Black EDTREFCL GR White EDTREFCL GR 1 Silver EDTREFCL GR 5 Left...

Страница 43: ...separately see Circuit Breaker on page 42 for options Title 24 Compliant Color Model Number Black EDTRICCL White EDTRICCL 1 Silver EDTRICCL 5 Black Title 24 Compliant EDTRICCLT24 White Title 24 Compli...

Страница 44: ...2A current limiting breakers One per circuit Amp Color Model Number 3A Black EDTRCL 3A White EDTRCL 3A 1 5A Black EDTRCL 5A White EDTRCL 5A 1 8A Black EDTRCL 8A White EDTRCL 8A 1 12A Black EDTRCL 12A...

Страница 45: ...pplies to T couplers too 1 Using a Phillips head screwdriver remove the screws that secure the cover to the coupler 2 Using a flat blade screwdriver loosen the two screws securing the red and black da...

Страница 46: ...6 Insert the red and black wires into their new location Tighten the wire retaining screws Gently pull on the wires to verify that they are properly connected Figure 2 New wire connection 7 Repeat ste...

Страница 47: ...Reconfiguring DMX Data Lines 45...

Страница 48: ...46 DataTrack System Planning and Installation Manual...

Страница 49: ...Reconfiguring DMX Data Lines 47...

Страница 50: ...111 683 Service UK service etceurope com Holzkirchen DE Tel 49 80 24 47 00 0 Service DE techserv hoki etcconnect com Hong Kong Tel 852 2799 1220 Service Asia service etcasia com Web etcconnect com 20...

Отзывы: