24
DataTrack System Planning and Installation Manual
Wiring In-line Feeds
1:
Strip ground wire and connect to a 0.25 in (6.35 mm) female quick disconnect terminal (not
supplied). Push terminal onto tap clamp at ground plate. Use provided green wire for connecting
between tap clamp and feed connector terminal.
2:
Strip white Neutral wire and connect to Neutral 1 terminal (N1) of feed connector. Clamp wire
using screw. See
Figure 19
.
:
Figure 19: In-line feed wiring
3:
Measure and strip a new wire (not provided) and connect N1 terminal (Feed Connector 1) to
N1 terminal (Feed Connector 2).
4:
Strip Hot 1 supply wire and connect to a 0.25 in (6.35 mm) female quick disconnect (not
supplied). Push onto the Line tap clamp on the current limiting circuit breaker.
5:
Connect load from current limiting circuit breaker to feed connector terminal L1 using provided
wire.
6:
Measure and strip a new wire (not provided) and connect L1 terminal (Feed Connector 1) to
L1 terminal (Feed Connector 2).
7:
Follow the same instructions for Neutral 2 and Hot 2.
Powering On DataTrack
1:
Place luminaires on track.
2:
Switch current limiting circuit breakers to ON position.
3:
Turn main power supply connector to the ON position.
• The current limiting circuit breakers will automatically switch to OFF if current ratings are
exceeded.
• If current limiting circuit breakers will not remain on: Reduce the wattage on the track so the
total wattage is less than the wattage specified on the current limiting circuit breakers. Turn
the current limiting circuit breakers to ON.
N1
L1
P E
L2
N2
Feed connector 2
Feed connector 1
CIRCUIT
BREAKER
CIRCUIT
BREAKER
Line
Load
Line
Load
PE
N1
L1
P E
L2
N2
HOT2
N2
PE1
HOT1
N1
Содержание EUTRAC
Страница 47: ...Reconfiguring DMX Data Lines 45...
Страница 48: ...46 DataTrack System Planning and Installation Manual...
Страница 49: ...Reconfiguring DMX Data Lines 47...