DataTrack System Planning and Installation Manual
Installing Current Limiting Feed Connector on a J-Box
The center line of the track must be on the center of the J-Box, and the mounting holes for the J-Box
must be at a 45º angle to the center line of the track.
1:
Remove the cover.
2:
Push current limiting circuit breakers into plate. Breakers ordered separately.
3:
Fasten plate to J-Box, passing supply wires through rectangular hole. Secure plate by securing
two mounting screws (not supplied) through plate and into J-Box.
4:
Attach wires per
Wiring End Feeds
on
page 23
.
5:
Slide track onto feed connectors. Make sure contact blades insert into the gap of the track bus
bars.
6:
Tighten feed connector locking screws.
7:
Fasten cover with supplied theft-resistant screws, taking caution to avoid pinching any wires.
See
Powering On DataTrack
on
page 24
.
Installing Current Limiting Feed Connector Using Flexible or Rigid
Conduit
1:
Remove the cover.
2:
Mark the center line of plate on ceiling to determine the mounting location of the feed
connector.
3:
Make a hole in the ceiling for the electrical connector in a position that coincides with one of the
round knockouts.
4:
Remove one round knockout where the power is to be passed through. Do not remove any other
knockouts.
5:
Push current limiting breakers into plate. Breakers ordered separately.
6:
Attach electrical connector (not supplied) to round knockout in plate.
7:
Pass supply wires through hole in ceiling and through electrical connector.
8:
Mount plate to ceiling using 2 plate mounting holes. Mounting hardware not supplied.
9:
Attach wires per
Wiring End Feeds
on
page 23
.
10:
Slide track onto feed connectors. Make sure contact blades insert into the gap of the track bus
bars.
11:
Tighten feed connector locking screws.
12:
Fasten cover with supplied theft-resistant screws, taking caution to avoid pinching any wires.
See
Powering On DataTrack
on
page 24
.
Note:
T24 (Title 24) current limiters have a 12" section of track installed on each end feed
when shipped. Straight couplers are required to splice the 12" sections with other
sections of track.
Note:
Current limiters are only ceiling mounted.