Assigning Echo Zones to Wireless Outputs
The OUTPUT STATUS LED's displays the assigned Zone number associated with the selected wireless output
as a count of lit LEDs. Zone assignment of wireless outputs allows combined control of Echoflex devices
with Echo zones that are configured for the same Space.
By factory default, the four Echoflex Outputs are configured to Zone 1 to Zone 4. Zones 1-16 may be
individually assigned to the wireless outputs.
When an wireless output is selected and the EEI is in Program Mode, indicated by a lit Program Mode LED,
the OUTPUT STATUS LED’s will display the selected output Zone. This is displayed according to the
following sequence:
• 1 green LED indicates Zone 1 for the selected Echoflex Output.
• When the selected Echoflex Output configured Zone is greater than 10, the additional Zone number
will indicate additively in a cycle. First, all LED’s will indicate (=10), then the remaining LED’s will
indicate (up to 6), followed by a long pause.
Configure Zone
1:
Place the EEI in Program Mode.
2:
Press the [SELECT] button until the wireless output to be configured is selected. The current zone
number configured to the selection displays on the OUTPUT STATUS LED's.
3:
Press the [ON] button to increase the zone number or press the [OFF] button to decrease the Zone
number. When the Zone number is greater than 10, a second set of LED's will indicate as an additive
process.
4:
When the desired zone number for the selection is displayed, you can choose to:
c: Press the [SELECT] button to change the selection to the next Echoflex Output and repeat the
process of configuring the zone number for the selection.
d: Exit Program Mode by pressing the [RECORD/PROGRAM] button.
5:
Press the [RECORD/PROGRAM] button to save the selection and exit Program Mode. The selected
Echoflex Input or Echoflex Output LED will blink to indicate the save process.
Note:
Only one Zone may be configured per Echoflex Output.