background image

 

 

 

             

 

 
 

 

 

User manual 

 

 

 
 

 
 

 

 
 

 
 

 

 
 

 
 

 

 
 

 
 

 

 
 

 
 

 

 
 

 
 

 

 
 

 
 

 

 
 

 
 

 

CU-DIN R 8-CH 16 A KNX 
EC10430299 

CU-DIN R 12-CH 16 A KNX 
EC10430305

 

CU-DIN R 4-CH 16 A KNX 

  EC10430282 

MA00629501 
06/2015 

Содержание CU-DIN KNK Series

Страница 1: ...User manual CU DIN R 8 CH 16 A KNX EC10430299 CU DIN R 12 CH 16 A KNX EC10430305 CU DIN R 4 CH 16 A KNX EC10430282 MA00629501 06 2015...

Страница 2: ...nction 20 5 5 2 Channel function parameters 20 5 5 3 Channel function time 22 5 5 3 2 Channel function Time staircase lighting 25 5 5 4 Channel function Scene 28 5 5 5 Channel function Threshold 30 5...

Страница 3: ...SER MANUAL 6 2 9 Objects Alarm for staircase lighting 49 6 2 10 Objects Scene 50 6 2 11 Objects Threshold 50 6 2 12 Objects Blinds 51 6 2 13 Objects Logic 52 6 2 14 Objects Heating 52 6 2 15 Objects F...

Страница 4: ...product only as intended as described in the user instructions Do not make any changes or alterations as this will render any warrantees null and void You should check the device for damage immediatel...

Страница 5: ...supply The CU DIN R 8 CH and CU DIN R 12 CH require an additional 24 V DC power supply if all of the channels are frequently operated at the same time but normal operation is also possible if there i...

Страница 6: ...umption EIB KNX operation 15 mA Current consumption EIB KNX standby 5 mA Power consumption EIB KNX operation 450 mW Power consumption EIB KNX standby 150 mW Output nominal values Type of device M R R...

Страница 7: ...the relays are recovered from the memory thereby enabling the relays to become active again This function is very useful when there is no additional DC power application in the system and the delay ti...

Страница 8: ...0 C 45 C 40 C 55 C 25 C 70 C Environmental conditions Humidity Max 93 non condensing Appearance design Modular DIN Rail modular installation Type M R R 4 CH R 8 CH R 12 CH Dimensions 90 x W x 65 Width...

Страница 9: ...ur lamp Uncompensated luminaire Parallel compensated 2800 W 2800 W Fluorescent lamp T5 T8 Uncompensated luminaire Parallel compensated DUO lamp 3500 W 2000 W 2000 W Dulux lamp Uncompensated luminaire...

Страница 10: ...e is to be protected against short circuits with a 16 A circuit breaker 1 Label area 2 Programming button programming LED 3 KNX EIB bus connector 4 Terminal for load connection 5 Contact position indi...

Страница 11: ...rangement e Protective devices e g fuses automatic protective devices etc to be connected to the load to avoid overloading 4 4 Maintenance and cautions Please read this user manual carefully before op...

Страница 12: ...EIB switch actuator database can be used with ETS3 0F ETS4 and ETS5 for the programmation The device types are CU DIN R 4 CH CU DIN R 8 CH and CU DIN R 12 CH and the database names are EC10430282_ CU...

Страница 13: ...CU DIN R 4 CH 16 A KNX CU DIN R 8 CH 16 A KNX 13 54 CU DIN R 12 CH 16 A KNX USER MANUAL 5 1 Program functions diagram...

Страница 14: ...ctivated the corresponding objects will be available One or more group addresses can be assigned to an object The association will connect group addresses to the object Type VD5 Max number of communic...

Страница 15: ...be used for a delay time of 2 200 s after the power is available again The default value is 2 seconds The min value is 2 seconds and the max value is 200 seconds Options 2 200 s After voltage recovery...

Страница 16: ...eter window some common functions can be set up After selecting a function and downloading the database to the device the device will work in accordance with the selected function Note take channel A...

Страница 17: ...the Switch Actuator mode Normally connected type This parameter is the choice of the type of access load Options Normally closed Normally opened Normally closed Contact in de energised state is closed...

Страница 18: ...for the ON time Alarm for time out Options No Yes No No alarm when time out Yes Alarm Alarm when time out 1 65 535 h This parameter sets the ON time alarm overflow time Options 1 65 535 h Alarm telegr...

Страница 19: ...e unchanged after bus voltage failure ON The channel will switch ON after bus voltage failure OFF The channel will switch OFF after bus voltage failure The Operation of switch after bus voltage recove...

Страница 20: ...up of the channel 5 5 2 Channel function parameters Fig 4 Channel function window In the factory defaults each channel function is disabled When enabled the channel function will be available Enable f...

Страница 21: ...ble the threshold function will be enabled Options Disable Enable Disable The threshold function is disabled Enable The threshold function is enabled Enable function blinds If set to Enable the blinds...

Страница 22: ...CU DIN R 8 CH 16 A KNX 22 54 CU DIN R 12 CH 16 A KNX USER MANUAL 5 5 3 Channel function time Fig 5 Time function window The time function includes three work modes as follows Options Flashing Staircas...

Страница 23: ...e control modes for this function Options Start with ON stop with OFF Start with OFF stop with ON Always flash start with ON OFF Start with ON stop with OFF Start flashing with ON and stop flashing wi...

Страница 24: ...0 and 100 0 is unlimited Position after flashing stops There are three options for the switch position after the flashing is stopped by the overflow counter Options Unchange ON OFF Unchange The switc...

Страница 25: ...t with 1 stop with 0 Start with 1 invalid with 0 Start with 1 0 can t stop Start with 1 stop with 0 When the received telegram value is 1 the staircase light is switched ON When the received telegram...

Страница 26: ...f 0 255 min Duration in minutes of the staircase lighting delay off time Time for off 0 59 sec Duration in seconds of the staircase lighting delay off time Warning staircase lighting ON OFF ON Options...

Страница 27: ...ay switch OFF delay protect ON delay and protect OFF delay Some special devices are used in a protective operation mode for ON or OFF Delay for switching ON 0 255 min Duration in minutes of the ON del...

Страница 28: ...y for protection OFF 0 59 sec Duration in seconds of the protected OFF delay Note 1 Protection ON delay If the light is turned off and then turned on again immediately the protection ON delay time wil...

Страница 29: ...al to a scene number The seventh bit of the telegram must be 0 to start the scene The scene is stored by receiving a telegram value from the bus The value of the telegram bit 0 6 is equal to a scene n...

Страница 30: ...itched ON OFF Channel is switched OFF 5 5 5 Channel function Threshold 5 5 5 1 Channel function 1 byte threshold There are two threshold values the upper threshold and lower threshold They can be set...

Страница 31: ...ge according to the input threshold value It has three ways to compare with the value of threshold Enable changes to threshold 1 over bus Options YES NO NO Do not allow changes to threshold 1 via bus...

Страница 32: ...tion is set to ON OFF The channel switch position is set to OFF Lower threshold Object value Upper threshold If the value of the receiving telegram from the bus is between the lower threshold and uppe...

Страница 33: ...s the 1 byte threshold function Enable changes to threshold 1 over bus Options YES NO NO Do not allow changes to threshold 1 via bus YES Allow changes to threshold 1 via bus Enable changes to threshol...

Страница 34: ...osition is set to ON OFF The channel switch position is set to OFF Lower threshold Object value Upper threshold If the value of the receiving telegram from the bus is between the lower threshold and u...

Страница 35: ...nd the second channel controls blinds DOWN In the above combination If blinds shall start going up then channel A switches ON and channel B switches OFF If blinds shall start going DOWN then channel B...

Страница 36: ...telegram value 0 1 from the bus and stops on timeout or receiving adjustment object telegram value Blinds UP 0 value The first channel for blinds UP or adjustment Options Channel A A current channel...

Страница 37: ...sets the blind adjustment time The maximum time is 5 s the minimum time is 50 ms Delay time for running direction changed When the running direction changes there is a delay time of 50 5000 ms The max...

Страница 38: ...CU DIN R 4 CH 16 A KNX CU DIN R 8 CH 16 A KNX 38 54 CU DIN R 12 CH 16 A KNX USER MANUAL Note A channel A L Logic connection R result...

Страница 39: ...1 has two inputs which are A and connect 1 Con1 The output of logic block 1 is connected to the input of logic block 2 Logic block 2 has two inputs which are connect 2 Con2 and output of logic block...

Страница 40: ...asses through logic block 1 to logic block 2 by the value of Con1 set to 1 A cannot pass through logic block 1 to logic block 2 until the value of Con1 is set to 1 the output of logic block 1 keeps th...

Страница 41: ...ection 2 after bus voltage recovery Set the value of logic connection 2 after bus voltage recovery Options 0 1 0 Initialisation logic connection 2 value is 0 1 Initialisation logic connection 2 value...

Страница 42: ...6 A KNX USER MANUAL 1 bit PWM control valve 0 OFF 10 26 20 51 30 77 40 102 50 128 60 153 70 179 80 204 90 230 100 ON 1 byte PWM control valve x x 0 255 X 0 OFF 1 25 0 26 50 10 51 76 20 77 101 30 102 1...

Страница 43: ...ons Normally closed Normally opened Normally closed Normally closed heating Normally opened Normally opened heating Switch state on bus voltage failure Three options can be set by the user Options Unc...

Страница 44: ...le Disable statistics ON counter Enable Enable statistics ON counter PWM cycle time set 1 65 535 min Options 1 65 535 min The minimum cycle time is 1 minute PWM cycle time set 0 59 sec Options 0 59 s...

Страница 45: ...0 102 50 128 60 153 70 179 80 204 90 230 100 ON Running automatically after bus voltage recovery Options No Defined value Recovery No PWM not running automatic power on Defined value PWM running by se...

Страница 46: ...pe 0 General Send cycles C R T EIS1 DPT 1 003 1 bit This communication object is always active and valid Invert the value and send telegram to bus in next frame e g last telegram value is 1 next teleg...

Страница 47: ...t uses the channel A response status if channel status is ON then the response status value is 1 otherwise the status value is 0 Table 4 Response 6 2 2 Objects R W statistics for time NO Object name F...

Страница 48: ...U DPT 12 001 4 bytes This communication object is used for statistics ON time of the channel A It can be read write via bus by setting this function active Table 7 Read write statistics ON counter 4 b...

Страница 49: ...S10 DPT 7 005 2 byte This communication object is used to modify the staircase lighting running time Allow modification to staircase lighting time via bus by setting this function activity Table 11 Ch...

Страница 50: ...111111 No 1 64 Example Hexadecimal 00h call scene 1 If scene is allocated 01h call scene 2 If scene is allocated 3Fh call scene 64 If scene is allocated 80h store scene 1 If scene is allocated 81h sto...

Страница 51: ...12 Objects Blinds NO Object name Function Flags Data type 24 Output A Moving for Blinds 0 UP 1 DOWN C W U EIS1 DPT 1 008 1 bit This communication object controls blind movement UP DOWN The blinds mov...

Страница 52: ...ctions include AND OR XOR and GATE Table 16 Logic 6 2 14 Objects Heating NO Object name Function Flags Data type 10 Output A Heat with 1 bit control C W U EIS1 DPT 1 001 1 bit If the heating actuator...

Страница 53: ...uring material defects in ESYLUX devices for a period of three years from the date of manufacture This guarantee is independent of your legal rights with respect to the seller of the device The guaran...

Страница 54: ...8 CH 16 A KNX 54 54 CU DIN R 12 CH 16 A KNX USER MANUAL because the guarantee has expired or the fault is not covered by the guarantee then the guarantor may attempt to repair the device for you for a...