Page 24 of 55
VERTICAL VENT TABLE
(All values are in feet)
EXAMPLES MINUMUM VERTICAL (V1 + V2 + V3) MAXIMUM HORIZONTAL (H1 + H2)
4’
10’
8’
20’
MAXIMUM VERTICAL HEIGHT = 34’
MAXIMUM HORIZONTAL OFFSETS = 20’
MAXIMUM 90
°
ELBOWS PERMITTED = 4
HORIZONTAL VENT TABLE
(All values are in feet)
EXAMPLES MINUMUM VERTICAL (V1) MAXIMUM HORIZONTAL (H1 + H2 + H3 + H4)
4’
10’
8’
20’
NOTE: All vent dimensions are measured from the
appliance surface where the vent connects to the point
where exhaust gases exit the termination.
REMARQUE: Toutes les dimensions sont mesurées à
partir d'aération de la surface de l'appareil où l'évent se
connecte au point où les gaz d'échappement de sortie de
la résiliation.