Please connect the refrigerant pipe as follows:
B
A
Vacuum pump
C
Pressure gauge
Refrigerant pipe
connection
A
Connect the refrigerant piping to the indoor unit.
B
Connect the other ends of the refrigerant pipe
to the outdoor unit.
4. Installation Walkthrough
4.6. Refrigerant Pipework
Radius 15 cm
IMPORTANT:
The radius of pipe bends cannot be less than 15 cm.
Use a cardboard/paper template to verify it is above this.
Run the power cord through the pipe as it bends.
Create the bends carefully and gradually.
Do not bend the pipe against an edge.
4.6.3.Installation: