4. Installation Walkthrough

4.1.  Sanitary Hot Water Configurations 

High temperature hot water export

Water mixture 

valve

Magnesium rod

T/P valve

City water

Water from heat pump

Water to heat pump

4.1.2.Configuration 2

In this configuration, hot water from the heat pump circuit runs through the coils in the tank.
Sanitary water fills the tank and is heated by the coils before exiting the tank towards the shower head.
This configuration also does not require sanitization.

The primary advantage to this configuration is that it can supply a greater volume of sanitary hot water.

Disadvantages include:

• 

The coil may create enough resistance to water flow that a secondary heat pump could be needed,  

  

in order to ensure that a proper flow rate, efficiency, and proper operation are maintained.

• 

The capacity of the coils will need to be greater than or equal to the maximum output of the unit.

  (

Max. heat pump output occurs at 7˚C Air/45˚C Water)

This configuration is optimal for a heat pump that does not exceed 14kW.

50

Содержание AWH11-V6-SW

Страница 1: ...ump DC Inverter Air to Water Before operating this product please read the instructions carefully and keep this manual for future use User s manual User s manual AWH6 V6 SW AWH9 V6 SW AWH11 V6 SW AWH13 V6 SW ...

Страница 2: ...2 ...

Страница 3: ...loded Views 3 Assembly Configurations Assembly Configuration Selection Flowchart Assembly Drawings Wiring and Software 4 Installation Walkthrough 4 1 Sanitary Hot Water Applications 4 2 Heating and Cooling Circuits 4 3 Indoor Unit Installation 4 4 Outdoor Unit Installation 4 5 Wiring 4 6 Refrigerant Pipework 4 7 Water Pipework 4 8 Test Run 5 Appendix A Wiring 5 3 6 8 9 10 11 11 13 15 19 19 20 49 4...

Страница 4: ... so please contact your local distributor Included Accessories Screws 1 2 3 4 5 X1 X1 X1 X2 X10 4 Temperature TC Water Sensor Temperature Sensor for cooling and heating TR Room Temperature Sensor for sanitary hot water TV 1 2 Water Temperature Sensors for Mixture Valves Sensor Communication Cable Communication Cable between Indoor and Outdoor Unit TR Room 1 2 6 7 8 9 10 11 X1 X1 X1 X2 X4 X1 ...

Страница 5: ...n given explicit prior consent in the form of writing Installation attempts of this system by anyone other than a properly trained and licensed professional Negligence of properly worn personal protection safety glasses gloves etc while performing installation maintenance or servicing of this product SAFETY The operation of this system during ambient temperatures which are below or beyond the temp...

Страница 6: ...Be sure to read this manual before use For sanitary hot water please always add a mixture valve before water tap and set it to proper temperature Ground wire Use a dedicated socket for this unit otherwise malfunction may occur The power supply to the unit must be grounded Do not touch the air outlet grill when fan motor is running Do not touch the power plug with wet hands Never pull out the plug ...

Страница 7: ... damages maybe caused Be aware fingers might be hurt by the fin of the coil 7 This marking indicates that this product should not be disposed with other household wastes throughout the EU To prevent possible harm to the environment or human health from uncontrolled waste disposal recycle it responsibly to promote the sustainable reuse of material resources To return your used device please use the...

Страница 8: ...nit Indoor unit Filter Water pump Heat exchanger Power supply Four way vavle Compressor Three way valve Refrigerant Filter T connector Fan motor Pressure check valve Evaporator Heating Cooling 8 1 Introduction 1 3 Functioning Principles ...

Страница 9: ...tions should be a variation of this master system drawing All suggested assembly variations are given in Chapter 3 Name Symbol Name Symbol Temp Sensor Safety valve Kit Ball valve Water filter Air purging valve Water pump Mixing valve Motorized valve Expansion tank Note Dotted lines mean able to be controlled by the Heat Pump ...

Страница 10: ...Water Heat Pump Unit Noise Level Indoor Outdoor 35 56 dB A AWH13 V6 SW 12 6 3 89 4 2 12 6 926 3072 3 89 4 77 11 5 3 08 3 76 11 5 1267 3723 2 97 3 28 10 3 3 29 4 29 10 37 957 3156 3 29 4 63 7 9 2 63 2 34 7 91 1000 3012 2 33 3 12 4200 150 2 30 59 AWH6 V6 SW 6 21 4 05 2 19 6 21 540 1530 4 05 5 87 5 8 3 22 2 05 5 8 640 1810 3 22 4 12 5 81 3 51 2 05 5 81 768 2105 3 15 4 71 4 5 2 52 1 59 4 5 614 1740 2 ...

Страница 11: ...Water Pump Door Water inlet Water outlet Air purging valve Operation panel Refrigerant Connector 1 2 5 8 AWH6 V6 SW AWH9 11 13 V6 SW Refrigerant Connector 3 8 3 8 AWH6 V6 SW AWH9 11 13 V6 SW Cable clip Cable gland Hinge Receiving signal antenna Sensor fixture Needle valve for service ...

Страница 12: ...its 12 Air inlet Air inlet Air outlet Valve cover Refrigerant connector 1 2 AW6 V6 SG AW9 V6 SG AW11 V6 SG Handle Valve cover Refrigerant connector 5 8 Air inlet Air inlet Air outlet Air outlet Handle 2 1 Functional Diagrams AW13 V6 SG ...

Страница 13: ...iew of the Units 2 2 Outlines and Dimensions Outlines and dimensions Unit mm Indoor Outdoor AW6 V6 SG AW9 V6 SG Unit mm Refrigerant connector dimension 1 4 and 1 2 AWH6 V6 SW AWH9 V6 SW 3 8 and 1 2 AWH6 V6 SW AWH9 V6 SW AWH11 V6 SW AWH13 V6 SW ...

Страница 14: ...sion 3 8 and 5 8 Unit mm 1195 1171 407 740 159 1058 1124 460 Refrigerant connector dimension 3 8 and 1 2 904 343 414 763 964 1044 Unit mm Outdoor AW11 V6 SG Outdoor AW13 V6 SG 430 2 Overview of the Units 2 2 Outlines and Dimensions ...

Страница 15: ...r flow switch Refrigerant expansion tank Fixture of plate heat exchanger Insulation panel Sensor fixture Cable gland Refrigerant connector Hinge WIFI module Receiving signal antenna Casing NO Name NO Name 2 3 Exploded view 2 Overview of the Units 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 12 Magnet 23 Needle valve for service Plate for refrigerant connector Cable clip Air purging ...

Страница 16: ...peration panel Decorative panel Door Electric box cover Electric box Plate heat exchanger Water pump Water flow switch Fixture of plate heat exchanger Insulation panel Sensor fixture Cable gland Refrigerant connector Hinge WIFI module Receiving signal antenna Casing NO Name NO Name 12 Magnet Needle valve for service Plate for refrigerant connector Cable clip Air purging valve ...

Страница 17: ...an Front panel Motor bracket Column support Four way valve Air guide Outdoor motor 1 2 3 4 5 6 7 8 9 Electrical box Electric box cover 10 11 Top panel Big handle Back panel Bulkhead Bulkhead 3 8 AW9 11 V6 SG Valve Condenser Compressor Compressor heater Feet Eev coil Condebser heater Electrical expansion valve Bottom plate 21 22 Valve cover Right plate 16 Valve 1 4 Valve AW6 V6 SG 2 3 Exploded view...

Страница 18: ...or motor Air guide 31 32 1 2 3 4 5 6 7 8 9 Top panel Coil and ambient temperature sensor Condenser 10 11 12 22 33 Bulkhead Compressor Handle Suction temperature sensor Bottom plate Valve plate 5 8 Valve Compressor discharge temperature sensor Sperator 3 8 Valve Terminal block Crankcase heater PFC transducer EEV controller Condenser heater 4 Way valve Electronic expansion valve Transformer EEV temp...

Страница 19: ...agrams with software instructions Beginning from the green Start Here bubble follow the appropriate arrows to each question which are dependent on the needs of the user The corresponding assembly instructions will be found by turning to the page number in the end bubble Note The instructions in this section are meant to achieve the minimum requirements for successful system operation only For more...

Страница 20: ...guration matches the assembly drawing depicted on the right for a one temperature zone without domestic hot water setup Note Refer to the next page for wiring and software operation instructions Name Symbol Name Symbol Temp Sensor Safety valve Kit Ball valve Water filter Air purging valve Water pump Mixing valve Motorized valve Expansion tank Note Dotted lines mean able to be controlled by the Hea...

Страница 21: ...s 1 Set the needed working modes of the unit via the menu H 2 If no heating curve is desired 3 Locate and activate the buffer tank and appropriate pumps under H 1 Setting a heating curve H Configuring the set water heating temperatures 2 Temperature configuration options for Heating Cooling circuit 1 are found under C Configuring the set water cooling temperature if applicable ...

Страница 22: ...ooling only through the use of a two way motorized valve Note For the cooling only or heating only circuit a motorized two way valve can be connected to the unit to cut the water supply during heating or cooling operation Refer to the next page for wiring and software operation instructions Name Symbol Name Symbol Temp Sensor Safety valve Kit Ball valve Water filter Air purging valve Water pump Mi...

Страница 23: ...s 1 Set the needed working modes of the unit via the menu H 2 If no heating curve is desired 3 Locate and activate the buffer tank and appropriate pumps under H 1 Setting a heating curve H Configuring the set water heating temperatures 2 Temperature configuration options for Heating Cooling circuit 1 are found under C Configuring the set water cooling temperature if applicable ...

Страница 24: ...24 3 Assembly Configurations Drawing 2 Software Basic Settings continued 4 The location of the configuration for heating only or cooling only system is under ...

Страница 25: ...he Heat Pump Notice The Fan Coil Unit Floor Heating System and Radiator are placeholder distribution systems only and can be substituted by any other appropriate distribution systems Please ensure that the configuration matches the assembly drawing depicted on the right for a two temperature zone without domestic hot water setup Note Refer to the next page for wiring and software operation instruc...

Страница 26: ...H 2 If no heating curve is desired 3 Locate and activate the buffer tank and appropriate pumps under H 1 Setting a heating curve H Configuring the set water heating temperatures 2 Temperature configuration options for Heating Cooling circuit 1 are found under C Configuring the set water cooling temperature if applicable For connection for mixing valve 2 please refers to the appendix A on page 75 7...

Страница 27: ...ing curve is desired Note This pair of settings will interpret Heating Cooling Circuit 2 as the low demand distribution system requiring a lower set temperature for heating and higher set temperature for cooling 4 1 Activate the mixing valve to manage the second circuit C Configuring the set water cooling temperature if applicable 4 Temperature configuration options for Heating Cooling circuit 2 a...

Страница 28: ... Pump Please ensure that the configuration matches the assembly drawing depicted on the right for a two temperature zone without domestic hot water setup that includes a component circuit capable of heating or cooling only through the use of a two way motorized valve Note For the cooling only or heating only circuit a motorized two way valve can be connected to the unit to cut the water supply dur...

Страница 29: ...H 2 If no heating curve is desired 3 Locate and activate the buffer tank and appropriate pumps under H 1 Setting a heating curve H Configuring the set water heating temperatures 2 Temperature configuration options for Heating Cooling circuit 1 are found under C Configuring the set water cooling temperature if applicable For connection for mixing valve 2 please refers to the appendix A of this manu...

Страница 30: ...n of the configuration for heating only or cooling only system is under H 1 Setting a heating curve H 2 If no heating curve is desired 5 1 Activate the mixing valve to manage the second circuit C Configuring the set water cooling temperature if applicable Note This pair of settings will interpret Heating Cooling Circuit 2 as the low demand distribution system requiring a lower set temperature for ...

Страница 31: ...uration matches the assembly drawing depicted on the right for a two temperature zone without domestic hot water setup that utilizes the secondary pump for a heating only operation Refer to the next page for wiring and software operation instructions Name Symbol Name Symbol Temp Sensor Safety valve Kit Ball valve Water filter Air purging valve Water pump Mixing valve Motorized valve Expansion tank...

Страница 32: ...H 2 If no heating curve is desired 3 Locate and activate the buffer tank and appropriate pumps under H 1 Setting a heating curve H Configuring the set water heating temperatures 2 Temperature configuration options for Heating Cooling circuit 1 are found under C Configuring the set water cooling temperature if applicable For connection for mixing valve 2 please refers to the appendix A of this manu...

Страница 33: ...H Configuring the set water heating temperatures H 1 Setting a heating curve H 2 If no heating curve is desired 4 1 Activate the mixing valve to manage the second circuit C Configuring the set water cooling temperature if applicable Note This pair of settings will interpret Heating Cooling Circuit 2 as the low demand distribution system requiring a lower set temperature for heating and higher set ...

Страница 34: ...ration matches the assembly drawing depicted on the right for a one temperature zone setup that includes domestic hot water Note Refer to the next page for wiring and software operation instructions Name Symbol Name Symbol Temp Sensor Safety valve Kit Ball valve Water filter Air purging valve Water pump Mixing valve Motorized valve Expansion tank Note Dotted lines mean able to be controlled by the...

Страница 35: ...s 1 Set the needed working modes of the unit via the menu H 2 If no heating curve is desired 3 Locate and activate the buffer tank and appropriate pumps under H 1 Setting a heating curve H Configuring the set water heating temperatures 2 Temperature configuration options for Heating Cooling circuit 1 are found under C Configuring the set water cooling temperature if applicable ...

Страница 36: ...Configurations Drawing 6 Software Basic Settings continued 4 Double check to ensure that the Domestic Hot Water option is enabled under Configure the desired setpoint for water temperature default set to 50 C 5 36 ...

Страница 37: ...ng or cooling only through the use of a two way motorized valve Note For the cooling only or heating only circuit a motorized two way valve can be connected to the unit to cut the water supply during heating or cooling operation Refer to the next page for wiring and software operation instructions Name Symbol Name Symbol Temp Sensor Safety valve Kit Ball valve Water filter Air purging valve Water ...

Страница 38: ...s 1 Set the needed working modes of the unit via the menu H 2 If no heating curve is desired 3 Locate and activate the buffer tank and appropriate pumps under H 1 Setting a heating curve H Configuring the set water heating temperatures 2 Temperature configuration options for Heating Cooling circuit 1 are found under C Configuring the set water cooling temperature if applicable ...

Страница 39: ...Settings continued Double check to ensure that the Domestic Hot Water option is enabled under 5 The location of the configuration for heating only or cooling only system is under 4 Configure the desired setpoint for water temperature default set to 50 C 6 ...

Страница 40: ...ration matches the assembly drawing depicted on the right for a two temperature zone setup that includes domestic hot water Note Refer to the next page for wiring and software operation instructions Name Symbol Name Symbol Temp Sensor Safety valve Kit Ball valve Water filter Air purging valve Water pump Mixing valve Motorized valve Expansion tank Note Dotted lines mean able to be controlled by the...

Страница 41: ...H 2 If no heating curve is desired 3 Locate and activate the buffer tank and appropriate pumps under H 1 Setting a heating curve H Configuring the set water heating temperatures 2 Temperature configuration options for Heating Cooling circuit 1 are found under C Configuring the set water cooling temperature if applicable For connection for mixing valve 2 please refers to the appendix A of this manu...

Страница 42: ...g a heating curve H 2 If no heating curve is desired 4 1 Activate the mixing valve to manage the second circuit Note This pair of settings will interpret Heating Cooling Circuit 2 as the low demand distribution system requiring a lower set temperature for heating and higher set temperature for cooling Dependent on whether cooling is needed H configuring the set water heating temperatures 3 cont Co...

Страница 43: ... or cooling only through the use of a two way motorized valve Note For the cooling only or heating only circuit a motorized two way valve can be connected to the unit to cut the water supply during heating or cooling operation Refer to the next page for wiring and software operation instructions Name Symbol Name Symbol Temp Sensor Safety valve Kit Ball valve Water filter Air purging valve Water pu...

Страница 44: ...H 2 If no heating curve is desired 3 Locate and activate the buffer tank and appropriate pumps under H 1 Setting a heating curve H Configuring the set water heating temperatures 2 Temperature configuration options for Heating Cooling circuit 1 are found under C Configuring the set water cooling temperature if applicable For connection for mixing valve 2 please refers to the appendix A of this manu...

Страница 45: ...is desired 5 1 Activate the mixing valve to manage the second circuit Note This pair of settings will interpret Heating Cooling Circuit 2 as the low demand distribution system requiring a lower set temperature for heating and higher set temperature for cooling Dependent on whether cooling is needed H configuring the set water heating temperatures 3 cont Configure the water pump to operate for heat...

Страница 46: ...izes the secondary pump for a heating only operation Note For the heating only circuit a motorized two way valve can be connected to the unit to cut the water supply during heating operation Refer to the next page for wiring and software operation instructions Name Symbol Name Symbol Temp Sensor Safety valve Kit Ball valve Water filter Air purging valve Water pump Mixing valve Motorized valve Expa...

Страница 47: ... H 2 If no heating curve is desired 3 Locate and activate the buffer tank and appropriate pumps under H 1 Setting a heating curve H Configuring the set water heating temperatures 2 Temperature configuration options for Heating Cooling circuit 1 are found under C Configuring the set water cooling temperature if applicable For connection for mixing valve 2 please refers to the appendix A of this man...

Страница 48: ...und under H 1 Setting a heating curve H 2 If no heating curve is desired 4 1 Activate the mixing valve to manage the second circuit Note This pair of settings will interpret Heating Cooling Circuit 2 as the low demand distribution system requiring a lower set temperature for heating and higher set temperature for cooling H configuring the set water heating temperatures 3 cont Configure the water p...

Страница 49: ...uit floods the tank This submerses the coils which run the shower water circuit resulting in a heat exchange interaction A mixing valve ensures that temperatures do not exceed 60 The primary advantages of this application include Sanitization is not necessary since the sanitary hot water is heated by going through the coils Direct connection between heat pump and tank ensuring effective water flow...

Страница 50: ...e shower head This configuration also does not require sanitization The primary advantage to this configuration is that it can supply a greater volume of sanitary hot water Disadvantages include The coil may create enough resistance to water flow that a secondary heat pump could be needed in order to ensure that a proper flow rate efficiency and proper operation are maintained The capacity of the ...

Страница 51: ...ater circulation pump by connecting it to port P3 This configuration will ensure a sufficient volume as well as flow rate of hot sanitary water at the additional cost of adding the plate heat exchanger Whichever application is chosen it is recommended to install a manual mixture valve between the city water inlet and hot water outlet This will maximize utilization of hot water from the tank while ...

Страница 52: ...nsure the heat pump unit provides a stable and sufficient water flow rate Minimize fluctuation of the system s heating cooling load by storing unused heat Increase capacity of water volume distribution which helps ensure proper heat pump operation If the method of hot water distribution is capable of dispersing a large enough flow rate a buffer tank can be excluded from installation into the confi...

Страница 53: ...g the temperatures for circuits 1 and 2 can be done via the Heating and Cooling Circuit menus If only one circuit is desired then Heating and Cooling Circuit 2 can be set to OFF 4 2 1 Heating Cooling Circuits The basic understanding of these settings is found under your the software section of your particular assembly walkthrough in Chapter 3 A more detailed explanation can be located in the user ...

Страница 54: ... via the TV1 or TV2 until the value set under the above menus is achieved TV1 and or TV2 should be activated on the installer s level via the Heating and Cooling Circuit menu Note A mixing valve is needed if The system has two circuits that require different water temperatures The heat pump will have to take the higher lower depending on whether heating cooling settings of the two circuits as the ...

Страница 55: ...de or after the set temperature is reached If Buffer Tank IS checkmarked both P1 and P2 will work as long as there is demand from the distribution system as per the pump setting The following must also be fulfilled Actual temperature in the buffer tank detected via TC is equal or above 20 C in heating Actual temperature in the buffer tank detected via TC is equal or below 23 C in cooling Even if t...

Страница 56: ...d downwards The indoor unit must operate in a dry well ventilated location There should be no volatile corrosive or flammable liquids or gases nearby Ideally the unit should be as close as possible to the water supply system Try and leave enough space in the area around the unit to simplify future maintenance 2 3 4 5 The minimum dimensions of surrounding gaps suitable for the unit to operate corre...

Страница 57: ...on 1 Take out the expansion bolts and mounting board accessory Place the mounting board on the wall horizontally Mark the bolting location onto the wall 2 Drill holes with the proper diameter for the bolts to catch through 3 Unscrew the nuts from the expansion bolts 4 Loosely fix the mounting board onto the expansion bolts Do not tighten yet 5 Using a hammer tap the expansion bolts into the drille...

Страница 58: ...le liquids or gases nearby Do not place the unit nearby to bedrooms and living rooms There will be noise when it is running In harsh climates of snow or sub zero temperatures ensure the unit is raised 50cm above ground It is recommended to install an awning above the unit to prevent snow from clogging open parts Ensure there is proper drainage around the unit Tilt the unit by 1cm m for rain water ...

Страница 59: ...t is fixed ensure each of the nuts are fully tightened Users should double check to make sure the unit s installation is sufficiently sturdy The bracket material can be stainless or galvanized steel aluminum or other proper substitutes The user can opt to use two concrete blocks or a raised concrete platform instead of a dedicated mounting bracket Ensure that the unit is securely fastened after in...

Страница 60: ...onnected directly to the city power supply Unit power supply For all units ensure that a cable of sufficient gauge is used found on nameplate E Outdoor unit power supply If the outdoor unit draws power from the indoor unit this terminal should be connected through cable between the appropriate ports see Appendix for wiring diagrams ...

Страница 61: ...mp for Heating Cooling Circuit 2 If there is an external water pump in heating cooling and hot water system it can be connected to these ports to be under the control of heat pump For user s side A B 4 Installation Walkthrough 4 5 Wiring 4 5 2 Explanation of Terminal Block 2 ...

Страница 62: ...ating source for both heating and DHW operation B Signal output to Hot Water Tank Backup Heater HWTBH which will be used as backup heating source for DHW operation only C Signal output to Heating Backup Heater hbh which will be used as backup heating source for Heating operation only D way motorized valve diverting the water 3 Application Side A B C D ...

Страница 63: ... external signal input Please refer to the user s manual for more detailed explanantions on ambient temperature setting For external signal input the external signal should be connected to Cool Mode Switch for cooling operation and Heat Mode Switch for heating operation 4 Installation Walkthrough 4 5 Wiring 4 5 4 Explanation of Terminal Block 4 A Signal cable between indoor and outdoor unit A ...

Страница 64: ...f before any wiring is done Cables should be properly fastened into place to prevent loosening from occurring No cable should be fastened to another The power supply should be compliant to all standards located in the rating label The power supply necessary cables and sockets should fully meet the input power requirements of the unit Installation sketch Signal cable between indoor and outdoor unit...

Страница 65: ...er cable s of suitable length that is compliant to all local safety regulations A Insert one end of this cable through the cable gland on the bottom of the indoor unit and connect it with the heat pump power supply terminals PE N L B Fasten the cable gland to ensure the cable won t loosen C Connect the other end of the cable to the city power supply B A PE N L ...

Страница 66: ...at is compliant to all local safety regulations A Insert one end of this cable through the cable gland on the bottom of the indoor unit and connect it with the AH power supply terminals PE N1 L1 B Fasten the cable gland to ensure the cable won t loosen C Connect the other end of the cable to the city power supply C B A PE N1 L1 ...

Страница 67: ...nit and connect it to A and B on the appropriate terminal block B Fasten the cable gland to ensure the cable won t get loosen Connect the other end of the cable to the terminal block on the outdoor unit A and B on the C indoor unit should be connected with A B and G on the outdoor unit otherwise communication failure error may occur 4 Installation Walkthrough 4 5 Wiring 4 Connect the signal cable ...

Страница 68: ...on the outdoor unit otherwise communication failure error may occur C Shown as Outdoor unit power supply on wiring diagram PE N L 4 Installation Walkthrough 4 5 Wiring 5 Connect the powercable between the indoor and outdoor unit Acquire a 3 core power cable of sufficient length that is compliant to all local safety regulations Notice When fixing the power cable with the wire clip take care to not ...

Страница 69: ...nect all sensors to the communication cables and insert the male end into the indoor unit through the cable glands Connect them to the female quick connectors inside the indoor units Place all sensors in the correct positions After everything is connected fasten the cable glands to prevent cables from loosening 7 Re install the electrical box cover as well as the small handle on the back of the ou...

Страница 70: ...erwise refrigerant leaks 4 6 2 Precautions Because the refrigerant pipe transfers heat to the entire system any insufficient vacuuming and or leakage of the refrigeration system will lead to decreased performance Therefore please ensure the following Select a high quality refrigerant pipe that conforms to the pressure standards of Refrigerant R410A Insulate the pipe before connecting it Avoid bend...

Страница 71: ...her ends of the refrigerant pipe to the outdoor unit 4 Installation Walkthrough 4 6 Refrigerant Pipework Radius 15 cm IMPORTANT The radius of pipe bends cannot be less than 15 cm Use a cardboard paper template to verify it is above this Run the power cord through the pipe as it bends Create the bends carefully and gradually Do not bend the pipe against an edge 4 6 3 Installation ...

Страница 72: ...ge shows a negative pressure reading turn off the vacuum pump and the gauge Disconnect the tube ends of pressure gauge and install the copper nut back to the high pressure connection port Remove the copper nut from the gas and liquid valves open the valves all the way using a hexagon spanner Check for any leakage using a detector or soapy water If no leakage is detector retighten the the copper nu...

Страница 73: ...ter on easier 4 7 2 Insulation All pipes running hot water should be well insulated No gaps should exist between insulation and outer pipe Keep the check valves uncovered for future maintenance Before finishing ensure that there is sufficient pressure to send water to the required heights If not a water pump can be added in order to increase pumping head 4 7 3 Water Quality Standards Water should ...

Страница 74: ...onnections and ensure they are secure Make sure there are no leaks in the piping and the space is well ventilated Fix any problems above if they occur If everything above is satisfied the unit can start up 2 3 4 5 6 7 8 4 8 2 Starting Up When the installation of the unit is completed all water system pipes are confirmed to be well connected air purging is done there are no leakages or other proble...

Страница 75: ...ing valve 0 10V DC Control Signal for mixing valve 1 Connection of Water Mixing Valve 1 Power Siwtch Indoor PCB Power Siwtch COM V Indoor PCB Cn217 Port 24V DC Power Supply for mixing valve 0 10V DC Control Signal for mixing valve 1 Connection of Water Mixing Valve 1 Power Siwtch Indoor PCB ...

Страница 76: ...76 Appendix A Wiring Indoor PCB Re2 2 way motorized valve L N Connection of 2 way motorized valve N from power supply or parallel to any N connector on terminal block ...

Страница 77: ...7 Indoor AWH6 V6 SW TAKE CARE The specifications are subject to change without prior notice For actual specifications of the unit please refer to the specification stickers on the unit Appendix B Wiring ...

Страница 78: ...9 V6 SW AWH11 V6 SW AWH13 V6 SW TAKE CARE The specifications are subject to change without prior notice For actual specifications of the unit please refer to the specification stickers on the unit Appendix B Wiring ...

Страница 79: ...9 TAKE CARE The specifications are subject to change without prior notice For actual specifications of the unit please refer to the specification stickers on the unit Outdoor AW6 V6 SG Appendix B Wiring ...

Страница 80: ... The specifications are subject to change without prior notice For actual specifications of the unit please refer to the specification stickers on the unit Appendix B Wiring Outdoor AW9 V6 SG AW11 V6 SG AW13 V6 SG ...

Страница 81: ......

Страница 82: ...order to prevent damages to either the device or persons R120400676 V1 0 August 2018 Product specifications are subject to change with improvements without prior notice Please refer to the specification sticker on the unit for the most recent specifications Please refer to the contact information below for technical support and enquiries E mail Telephone ...

Отзывы: