MAINTENANCE AND DIAGNOSIS OF FAILURES
DOLFIN operator for sliding gates
65
3
FAILURE DIAGNOSIS
4
SCRAP
The operator, up until the end of its useful life,
must be dismounted at its location by an
installer who is as well qualified as the person
who completed the assembly, observing the
same precautions and safety measures. In this
manner possible accidents and damage to
adjacent facilities will be avoided.
}
The operator must be deposited in the appropriate
containers for subsequent recycling, separating and
classifying of the different materials in line with their
nature. NEVER deposit it in domestic rubbish or in
landfills which are not suitably controlled, as this will
cause environmental contamination.
Problem
Cause
Solution
The operator does not make
any movement when the key
devices are activated
Absence of system power supply
voltage
Reestablish the power supply
Electrical installation defective
Check that the installation does
not present any short-circuits or
cut-off points
The key for manual operation is in
unlock position (the display shows
StOP
)
Position the key in locking position
for motorised operation
The transmitter radio code is not
recorded in the operator
Correctly record the radio code
The transmitter batteries are flat
Replace the batteries
The gate does not open
(the display shows
C4
or
Ftço
)
The closing safety device (photocell or
strip) or its cabling are open or defective
Check the cabling and device
(photocell or safety strip)
The gate does not close
(the display shows
C5
or
Ftço
)
The opening safety device (photocell or
strip) or its cabling are open or defective
Check the cabling and device
(photocell or safety strip)
The gate cannot completely
close (or open)
The resistance of the gate has increased
when closing (or when opening)
Check the moving parts of the gate
and remove the resistance
The thrust of the operator during
closing (or opening) is too low
Using programming, increase the
opening or closing thrust
The belt is not correctly taut.
Tighten the belt correctly
The gate open/close programming has
not been carried out correctly
Correctly programme the open/
close
Содержание Dolfin DOS424E
Страница 2: ......
Страница 26: ...Actualizado 23 5 11 MANTENIMIENTO Y DIAGN STICO DE AVER AS 22 Manual de instalaci n...
Страница 48: ...Mis jour 7 9 11 MAINTENANCE ET DIAGNOSTIC DE PANNES 44 Manuel d installation...
Страница 70: ...Updated 5 9 11 MAINTENANCE AND DIAGNOSIS OF FAILURES 66 Installation Manual...
Страница 92: ...Actualizado 7 9 11 MANUTEN O E DIAGN STICO DE AVARIAS 88 Manual de instala o...
Страница 114: ...Erreka B Ibarreta s n 20577 Antzuola Gipuzkoa T 943 786 150 F 943 787 072 info erreka com www erreka com MSM 038 02...