DOLFIN operator for sliding gates
59
START UP AND PROGRAMMING
1
CONNECTION TO THE GRID
1
Connect the operator to the power supply.
2
Press the ENTER push button: the display should
light up.
Reset (
rS
):
after connecting the electricity power
supply and activating any of the key devices, the
gate closes to the stopper, with the stopper being
assigned the position "gate closed".
CHANGE OF TURNING DIRECTION:
if, when
carrying out the reset (
rS
), the gate opens instead of
closing, it is necessary to change the turning
direction by programming parameter
C1
(see “Initial
Conditions Programming (D1= “
C
”)” on page 60).
During programming, ensure there is no
person or object in the radius of action of the
gate and the operation mechanisms.
2
DISPLAY
Indications during operation:
D1 and D2:
CL
(static)
Gate closed
CL
(flashing)
Gate closing
OP
(static)
Gate open
OP
(flashing)
Gate opening
PC
(flashing)
Pedestrian gate closing
PO
(static)
Pedestrian gate open
PO
(flashing)
Pedestrian gate opening
XX
(countdown)
Gate on standby
StOP
Operator unlocked
PA
(static)
Pause (operation not complete)
rS
(static)
Gate searching for close position
D3 and D4:
C4
Opening safety device activated
C5
Closing safety device activated
E1
Encoder motor shutdown
F1
Thrust limit exceeded
bA
Battery working
Ftço
Photocells defective (pre-testing)
Indications during programming
D1 (Menus):
Shows the selected menu. The following
menus are available:
C
Prior Conditions menu
P
Programming menu
F
Main Functions menu
A
Advanced Functions menu
ç
Operation Counter
D2 (Parameters):
Shows each parameter of the selected D1 menu.
D3 - D4 (Parameter Values):
Shows the value or option of the selected D2
parameter.
Enter
Esc
D1
: Menus
display
D2
: Parameters
display
D3 - D4
: Parameter display value
The display goes off following a long period
without pressing any key on the control
board. Press the ENTER key to reactivate.
Содержание Dolfin DOS424E
Страница 2: ......
Страница 26: ...Actualizado 23 5 11 MANTENIMIENTO Y DIAGN STICO DE AVER AS 22 Manual de instalaci n...
Страница 48: ...Mis jour 7 9 11 MAINTENANCE ET DIAGNOSTIC DE PANNES 44 Manuel d installation...
Страница 70: ...Updated 5 9 11 MAINTENANCE AND DIAGNOSIS OF FAILURES 66 Installation Manual...
Страница 92: ...Actualizado 7 9 11 MANUTEN O E DIAGN STICO DE AVARIAS 88 Manual de instala o...
Страница 114: ...Erreka B Ibarreta s n 20577 Antzuola Gipuzkoa T 943 786 150 F 943 787 072 info erreka com www erreka com MSM 038 02...