InfraStyle / InfraStyle i - Installation Instructions
55
Installation
5.2.3 Unit address – ADR DIP switch
Each connected IR module is assigned a unique unit address. Each unit
address must only be assigned once so that the unit can be uniquely iden-
tified.
One IR relay box and 2 IR modules per cabin are supported. Control loops
for the three units are controlled simultaneously.
Typically, the relay box is assigned unit address 1. Additional modules are
assigned addresses 2 and 3 respectively in the IR modules.
5.2.4 Channels – DIP switches IR1 to IR3
IR emitters can be grouped into channel groups and controlled simultane-
ously. A group can comprise various IR emitters. Channels A-E are available
for these groups.
The assignment of the IR connections to a channel can be set globally, e.g.:
Standard channel group configuration
If emitters are connected to output IR-3 and emitters or foils are connected
to outputs IR-1 and IR-2, the DIP switches for the channel groups are set as
follows.
Do NOT combine dimmable and switchable IR emitters in one channel
group.
Address 1 (unit 1)
Address 2 (unit 2)
Address 3 (unit 3)
DIP switch 2-3 = ON
DIP switch 1-4 = ON
DIP switch 5 = ON
1
2
3
4
5
ADR
ON
1
2
3
4
5
ON
ADR
1
2
3
4
5
ON
ADR
Unit/module
Channel IR1 Channel IR2 Channel IR3
Module 1
A
A
C
Module 2
B
A
C
Module 3
D
D
E
Example
Channel IR1 to
IR3
1
2
3
4
5
Example – channel
A
A
ON
B
ON
C
ON
D
ON
E
ON
1
2
3
4
5
ON