X1
X2
F1
Example of the error message
for overheating limiter fuse (DE)
Attention!
Make sure not to confuse
the sensor cables at X2 connector!
This may cause the F2 fuse to burn,
for replacement see page 29.
Hole
Sauna ceiling
Jumper for heating time
limitation setting:
6 h, 12 h, unlimited
centre sensor housing in
the middle of the plank
Second temperature
sensor (optional)
Humidity sensor (op-
tional, only Econ H3)
sensor cables
Fig. 11
142°C
KTY 10/5
Sensor
Limiter
X2
weiß / white
rot / red
Fig. 12
6. After completed installation and correct
commissioning of the control unit, the line
for overtemperature protection must be
checked for short-circuits. In order to do this,
disconnect one of the white cables in the
sensor casing. The respective error message
shall appear in the display.
12:00
Sensor -
break
11
GB