POWER FACTOR CONTROLLER

RG3-15C/CS/CL/CLS

8

3.3 Selection of Proper Switching Sequence

There are 10 different program modes which determines the power ratio

sequence of the capacitor steps. The switching programs are given in the

table. If the step sequence is selected as in program 02(PS-02), many

identical connection components must be used. When a step sequence

between the 3rd and the 8th one is selected, less identical connection

components will be used. By selecting the 9th connection sequence,

different group powers can be achieved. In this sequence connection, the

rating of each capacitor step value may exceed that of the first by  a

maximum  amount  equal  to  the   preceding  capacitor  steps  value. By

using this setting, less capacitors will be used. When the 10th connection

sequence is selected, RG3-15C/CS/CL/CLS will calculate the capacitor

step power values automatically.RG3-12C/CS/CL/CLS  counts swithing

on&off times of all capacitor steps and so only the most necessary step

is switched on. Thus,  maximum  service  life  time  of  the  system  is

ensured.

NOTE: In the 10th program(PS-10), power values and

connection types(except the first step) of the single phase

capacitor steps(r, s, t, rst, oFF) can be set by user. In Auto

setup mode power values of all capacitor steps are measured

and connection types of the capacitor steps are detected

by the device. In all the connection sequences except the

10th one, only the 1st capacitor step power can be set. All

the other capacitor step values are calculated according to

the 1st capacitor steps power value.

Set the program option suitable for your system in this menu

.

Press the “SET” button for 3 s in order to enter the menu.

Using the 

“UP/DOWN”

 buttons, select the Program (Prog) menu.

When program menu is displayed, program LED turns on.

SAUE

If you want to leave the setup menu without making any other

changes, press the 

“ESC”

 button until 

“SAVE SEt yES”

 shows

on the screen. If you want to save the changes, press the 

“SET”

button. If not, press the 

“ESC”

 button.

Press the 

“SET”

 button to select the switching program.

Enter the desired program number between 01-10 and press the

“SET”

 button.

Using the 

“UP/DOWN”

 buttons, enter to another menu option

which you wish to change. If you are not going to change any

more settings, press the 

“ESC”

 button.

Press the “SET” button for 3 s in order to enter the menu.

P R O G R A M

SEQUENCE

01

02

03

04

05

06

07

08

09

*10

linear

1.1.1.1................

1.1.2.2................

1.2.2.2................

1.2.3.3................

1.2.4.4.................

1.1.2.4................

1.2.3.4................

1.2.4.8................

Capacitor step values are calculated automatically.

* Recommended switching program.

In order to decrease harmful effects of instant reactive power loads to the

relays and capacitors, delay time (in terms of seconds) for capacitor steps

is entered in this menu.

Switch-on delay time must be set according to system requirement in

order to achieve compensation targets and also to provide long life time

for contactors and capacitors.

3.4.a Switch-On Delay Time Setting

NOTE: t-on and t-of time periods must be set according to your systems

requirements. If t-on time is set very long, relay can not switch on until

the end of this time period and so target compensation ratios may not

be achieved. If t-on time is set too short, capacitor steps switch on&off

frequently in case of fast load variations and this will shorten the life

time of contactors and capacitors. For this reason, it is very important

to set these time periods according to your system’s requirement.

Using the 

“UP/DOWN”

 buttons, select the delay time menu

(dELy).

When delay time menu is displayed, time LED turns on.

3.4 Switching On&Off and Discharge Time Settings

Содержание RG3-15C

Страница 1: ...ischarge Time Settings 8 3 5 Power Value and Connection Type Settings for Capacitors 10 3 6 Current and Voltage Transformer Ratio Settings 12 3 7 Reset Settings 14 3 8 Alarm Settings 15 3 9 Resetting...

Страница 2: ...3 12C CS s housing There are no user servicable parts inside it RG3 12C CS is connected to the network by means of a current transformer Do not disconnect the current transformer terminals If you disc...

Страница 3: ...o the device at the same time RG3 15C CS CL CLS ile Yap labilecek l mler Phase Voltage L1 2 3 N Measurement Phase Current L1 2 3 N Measurement Cosj Value L1 2 3 N Measurement Average Ind Cap Cosj Valu...

Страница 4: ...23 C LED 24 25 26 27 28 29 30 If PROGRAM I LED is on in the menu the switching sequence can be set in the menu If PROGRAM I LED is on in the measuring mode the phase currents appear on their correspon...

Страница 5: ...L l2 k2 K L l3 k3 Alarm Relay Generator Input 110 250 V AC C12 C11 C10 C9 C8 C7 C5 C4 C3 C2 C1 C13 C14 C15 C6 RG3 15C CS Current value of 3 Phase fuses which are connected to protect the capacitors mu...

Страница 6: ...tched to the generator operation for any generator starts including the ones for maintaining purposes a b c After the device is energised it finds connection errors and corrects them automatically Pow...

Страница 7: ...the option on is selected in the automatic setup menu the automatic capacitor recognition will start without exiting the menu The step powers which are calculated after this process must always be che...

Страница 8: ...nection option To change this setting press the SET button When Auto connection is on the device controls its connection automatically at start up and corrects any existing measurement input errors If...

Страница 9: ...WN buttons select the Program Prog menu When program menu is displayed program LED turns on SAUE If you want to leave the setup menu without making any other changes press the ESC button until SAVE SE...

Страница 10: ...not press the ESC button Enter a value between 1 1800 seconds and then press SET button Using the UP DOWN buttons enter to another menu option which you wish to change If you are not going to change...

Страница 11: ...PS 10 is selected power value of the first capacitor step is measured and other steps power values are calculated according to selected program Note When setup parameter is selected as on in Auto menu...

Страница 12: ...until SAVE SEt yES shows on the screen If you want to save the changes press the SET button If not press the ESC button When PS 10 Program 10 is selected connection type and capacitor power value sett...

Страница 13: ...Transformer Ratio Setting To obtain accurate power values when calculating the capacitor step powers current and voltage transformer ratios must be entered correctly If these ratios are entered incor...

Страница 14: ...the screen If you want to save the changes press the SET button If not press the ESC button In this menu voltage transformer ratio can be set between 1 2000 For Example For a 34 5 kV 100 V transformer...

Страница 15: ...selected Reset LED turns on Press the SET button to enter reset rESEt setting options Press the SET button to set the alarm ALAr setting which is the first setting in the reset rESEt menu Select yES...

Страница 16: ...arm Setting 3 8 Alarm Settings In this menu overvoltage value is set between 0 300 V for Vtr 1 If this value is set as 0 this function is disabled 3 8 a a Overvoltage Setting SAUE If you want to leave...

Страница 17: ...the overvoltage delay time setting menu SAUE If you want to leave the setup menu without making any other changes press the ESC button until SAVE SEt yES shows on the screen If you want to save the ch...

Страница 18: ...e ESC button SAUE If you want to leave the setup menu without making any other changes press the ESC button until SAVE SEt yES shows on the screen If you want to save the changes press the SET button...

Страница 19: ...erthemenu Using the UP DOWN buttons find the alarm menu ALr When alarm menu is selected alarm LED turns on Press the SET button to enter the alarm ALr settings Using the UP DOWN buttons find over volt...

Страница 20: ...uttons SAUE If you want to leave the setup menu without making any other changes press the ESC button until SAVE SEt yES shows on the screen If you want to save the changes press the SET button If not...

Страница 21: ...the energy values can be entered with 0 1 kWh kVArh precision for both counters Resetting the energy counters can be done from this menu Energy counters can also be conditioned to work with the gener...

Страница 22: ...ut The conditioning of the energy counters is done in this menu There are 2 parameters If the gEn ACt no parameter is selected Energy Counter 1 and Energy Counter 2 will count simultaneously If the gE...

Страница 23: ...ud rate menu bAUd SAUE If you want to leave the setup menu without making any other changes press the ESC button until SAVE SEt yES shows on the screen If you want to save the changes press the SET bu...

Страница 24: ...n be changed and activated in this menu When the password is activated a pin code is always required before entering the menu Thus user password prevents any change to the settings of the device by un...

Страница 25: ...new password press the SET button Enter the new password again and press the SET button If you are going to change another setting return to the menu by pressing the SET button If you do not want to...

Страница 26: ...nics When Cosj values are displayed if DOWN button is pressed Total Inductive Cosj and Total Capacitive Cosj values are observed As you can see in the example below total inductive Cosj value is displ...

Страница 27: ...is phase is export active power Currents I and HAR LEDs on the display indicate that displayed values indicate current harmonic values By pressing the SET button repeatedly THD and odd numbered harmon...

Страница 28: ...are displayed if the DOWN button is pressed inductive reactive and capacitive reactive power values are observed As seen in the example below total reactive inductive power value is displayed on the...

Страница 29: ...import energy and the remaining numbers show the energy value such as 203385706 8 kWh While active import energy is displayed if the DOWN button is pressed active export energy is displayed In the ex...

Страница 30: ...ion Error Compensation Error Defected 1st capacitor step or loads are too variable Target Cosj is capacitive even when all capacitor steps are switched off Capacitor powers are not sufficient for targ...

Страница 31: ...long int unsigned long int long int 0000 0002 0004 0006 0008 000A 000C 000E 0010 0012 0014 0016 0018 001A 001C 001E 0020 0022 0024 0026 0028 002A 002C 002E 0030 0032 0034 0036 0 1 2 3 4 5 6 7 8 9 10...

Страница 32: ...6 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 PHASE 3 VOLTAGE VECTO...

Страница 33: ...00A5 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160...

Страница 34: ...800B 800C 800D 800E 8012 8013 8014 8015 8016 8017 8018 8019 801A 801E 801F 8080 8081 8082 8083 8084 8085 8086 8087 8088 8089 808A 808B 808C 808D 808E 808F 8090 8091 8092 8093 8094 8095 8096 8097 8098...

Страница 35: ...ION 1ST CAPACITOR STEP SWITCH ON OFF 2ND CAPACITOR STEP SWITCH ON OFF 3RD CAPACITOR STEP SWITCH ON OFF 4TH CAPACITOR STEP SWITCH ON OFF 5TH CAPACITOR STEP SWITCH ON OFF 6TH CAPACITOR STEP SWITCH ON OF...

Страница 36: ...R RG3 15C CS CL CLS 35 In the first column total reactive power values of 3 phase capacitors and in second third columns reactive power values of the capacitors in single phase system are shown CAPACI...

Страница 37: ...0 V AC 3 0 s Off 7 0 1 0 s Off 25 15 96 hours 1 1 1 9 600 Kbps no Operating Voltage Un Operating Voltage Range DU Operating Current Range DI Frequency Measurement Class Power Consumption Output Conta...

Отзывы: