POWER FACTOR CONTROLLER
RG3-15C/CS/CL/CLS
18
SAUE
If you want to leave the setup menu without making any other
changes, press the
ESC
button until
SAVE SEt yES
shows
on the screen. If you want to save the changes, press the
SET
button. If not, press the
ESC
button.
If total harmonic value of measured voltages exceeds the value which is
enterd from this menu and does not return to normal level during the entered
delay time(dELy), alarm relay switches on and harmonic LED( ) turns on.
3.8.d Harmonic Setting
The upper limit for the overvoltage harmonic value to set the harmonic
alarm is set in this menu.
3.8.d.a Overvoltage Harmonic Setting
Press the
SET
button for 3 sec. in order to enter the menu.
Using the
UP/DOWN
buttons, find the alarm menu(ALr). When
alarm menu is selected, alarm LED turns on.
Press the
SET
button to enter the alarm(ALr) settings.
Using the
UP/DOWN
buttons, find over voltage harmonic
menu(tHd) which is the fourth setting in the alarm menu.
In this menu, over voltage harmonic value(tHdV), delay time(dELy)
and switching off of the capacitor steps(StEP)
parameters are
set. In order to set these parametesers, press the
SET
button.
SAUE
If you want to leave the setup menu without making any other
changes, press the
ESC
button until
SAVE SEt yES
shows
on the screen. If you want to save the changes, press the
SET
button. If not, press the
ESC
button.
The first setting in this menu is the overvoltage harmonic (thdV)
value. Press the
SET
button to enter the overvoltage settings
menu.
Enter the overvoltage harmonic value between 0-99 % and press
the
SET
button.