POWER FACTOR CONTROLLER
RG3-15C/CS/CL/CLS
13
Using the
UP/DOWN
buttons, find current and voltage
transformer ratio menu (trF). When this menu is selected,
Transformer (VA/TRF) LED turns on.
Press the SET button for 3 s in order to enter the menu.
Press the
SET
button to enter to the CT and VT ratio setting
menu.
The first setting in the CT and VT ratio menu is the CT ratio menu.
Press the
SET
button to set CT ratio.
Enter CT ratio between 1-2000 and press the
SET
button. If you
do not want to set another parameter, press the
ESC
button. If
you are going to change another setting, enter the desired menu
option by using
UP/DOWN
buttons. If you do not want to set
another parameter, press the
ESC
button.
SAUE
If you want to leave the setup menu without making any other
changes, press the
ESC
button until
SAVE SEt yES
shows
on the screen. If you want to save the changes, press the
SET
button. If not, press the
ESC
button.
In this menu, voltage transformer ratio can be set between 1-2000.
For Example:
For a 34,5 kV / 100 V transformer, VT ratio must be set as 345.
NOTE:
Be aware that this value is entered as a ratio, not VT primary
or secondary value.
3.6.b Voltage Transformer Ratio Setting
Using the
UP/DOWN
buttons, enter the voltage transformer
ratio (Vtr) menu which is the second menu in CT and VT ratio
settings.
Press the
SET
button to set VT ratio.
Enter VT ratio between 1-2000 and press the
SET
button. If
you do not want to set another parameter, press the
ESC
button.
If you are going to change another setting, enter the desired menu
option by using
UP/DOWN
buttons. If you do not want to set
another parameter, press the
ESC
button.
SAUE
If you want to leave the setup menu without making any other
changes, press the
ESC
button until
SAVE SEt yES
shows
on the screen. If you want to save the changes, press the
SET
button. If not, press the
ESC
button.