POWER FACTOR CONTROLLER
RG3-15C/CS/CL/CLS
16
If on is selected:
When overvoltage error occurs, capacitor steps
stay switched on.
If off is selected:
When overvoltage error occurs, capacitor steps
stay switched off.
3.8.a.c Switch On or Switch Off Setting of Capacitor
Steps for Overvoltage Alarm Setting
In order to protect the capacitors from overvoltage, when an overvoltage
alarm occurs, capacitor steps switch on or switch off settings are done
in this menu.
If reactive/active energy ratio exceeds the preset value, an alarm occurs.
This ratio can be set for inductive/active and capacitive/active separately
between 0-99.9 %. If this value is set as 0, this function is disabled.
3.8.b
Reactive / Active Ratio Setting
In order to provide accurate compensation, the upper limit value of
capacitive/active ratio is entered in this menu. This value can be set between
0-99.9 %. If the capacitive/active ratio of the network exceeds the preset
value, an alarm occurs. If this value is set as 0, this function is disabled.
3.8.b.a
Capacitive Ratio Setting
The second setting in the voltage menu(UoLt) is the overvoltage
delay time(dELy). Press the
SET
button to enter the overvoltage
delay time setting menu.
SAUE
If you want to leave the setup menu without making any other
changes, press the
ESC
button until
SAVE SEt yES
shows
on the screen. If you want to save the changes, press the
SET
button. If not, press the
ESC
button.
Enter the over voltage delay time between 0-999.9 seconds. If
you are going to change another setting, return to the menu by
pressing the
SET
button. If you do not want to set another
parameter, press the
ESC
button.
The third setting in the voltage menu(UoLt) is the overvoltage
step setting(StEP). Press the
SET
button to enter the overvoltage
step setting menu.
Make a selection by using
UP
/
DOWN
buttons.
Using the
UP/DOWN
buttons, select
on
or
of
option and
press the
SET
button. Using the
UP/DOWN
buttons, enter
to another menu option which you wish to change. If you are not
going to change any more settings, press the
ESC
button.
SAUE
If you want to leave the setup menu without making any other
changes, press the
ESC
button until
SAVE SEt yES
shows
on the screen. If you want to save the changes, press the
SET
button. If not, press the
ESC
button.
Press the
DOWN
button in order to switch from overvoltage
menu to the overvoltage step menu(StEP).
Press the
SET
button for 3 sec. in order to enter the menu.
Using the
UP/DOWN
buttons, find Alarm (Alr) menu. When
Alarm
menu is selected, Alarm LED turns on.