When the device is energised for the first time, it checks for connection

errors. If there is a faulty connection, it corrects this fault in itself. In order

for the device to correct a connection fault, 3-phase voltage and current

connections of the device must be done.

NOTE:

 

If there are other loads than compensation connected to the

system, the device may not find the connection at the first try and may

need several tries. However, if the device is unable to complete the

automatic connection process step calculation process shouldn’t be

done.

          In order for the calculated capacitor powers to be accurate, the

current and voltage transformer ratios have to be entered correctly

before the automatic capacitor recognition process. If these ratios are

not entered by the user, they will be set as “1” by the device and the

capacitor step powers will be calculated according to these values(Refer

to page 12-CT and VT Ratio Settings).

After any connection faults are corrected by the device; if “Auto Setup”

option is set as 

“on”

, the device calculates the capacitor step powers

according to the selected program. If 10th program(P-10) is selected , all

of the capacitor step powers are measured seperately. If any other program

is selected, the device measures only the first capacitor step power and

then calculates the other step powers according to the selected

program

(Refer to page 7-Step Number Setting).

NOTE: If the option “on” is selected in the automatic setup menu, the

automatic capacitor recognition will start without exiting the menu.

The step powers which are calculated after this process must always

be checked.

Inductive load step powers can’t be calculated automatically for RG3-

15CL/CLS. Power values have to be entered manually.

Press 

“UP”

 or 

“DOWN”

 button

to select.

POWER FACTOR CONTROLLER

RG3-15C/CS/CL/CLS

3.1.b Automatic Capacitor Recognition Mode Setting

6

Press the “SET” button for 3 s in order to enter the menu.

Select 

“on”

 or 

“of”

 using the 

“UP”

 and

“DOWN”

  buttons(Select 

“on”

 for automatic

capacitor recognition).

Press 

“SET”

 button to set the parameters in “Auto” menu option.

To select the automatic operating mode, choose “

on

” with 

“UP”

or 

“DOWN”

 buttons and press “

SET

” button. To select the manual

operating mode, choose “

oF

” with 

“UP”

 or 

“DOWN”

 buttons and

press “

SET

” button.

The first setting in this menu is the operation mode(Operati). The

operation mode of the device is selected according to this option’s

on or off selection. Press 

“SET”

 button to change this setting.

In Auto Operatý menu, choose “Auto Setup” menu by pressing

the 

“UP”

 button.

The 2nd setting in this menu is the Auto Setup setting. The

automatic setup will or will not start according the options “on”

or “off” selection. To change this setting, press the SET button.

Numerical values of the parameters are set via buttons in

the display. The blinking digit indicates which digit will be

set. Numerical value of the related digit is increased or

decreased via 

“UP”

 or 

“DOWN”

 button. To set the next

digit, 

“SET”

 button is used. To go back to the previous

digit, 

“ESC”

 button is used.

Содержание RG3-15C

Страница 1: ...ischarge Time Settings 8 3 5 Power Value and Connection Type Settings for Capacitors 10 3 6 Current and Voltage Transformer Ratio Settings 12 3 7 Reset Settings 14 3 8 Alarm Settings 15 3 9 Resetting...

Страница 2: ...3 12C CS s housing There are no user servicable parts inside it RG3 12C CS is connected to the network by means of a current transformer Do not disconnect the current transformer terminals If you disc...

Страница 3: ...o the device at the same time RG3 15C CS CL CLS ile Yap labilecek l mler Phase Voltage L1 2 3 N Measurement Phase Current L1 2 3 N Measurement Cosj Value L1 2 3 N Measurement Average Ind Cap Cosj Valu...

Страница 4: ...23 C LED 24 25 26 27 28 29 30 If PROGRAM I LED is on in the menu the switching sequence can be set in the menu If PROGRAM I LED is on in the measuring mode the phase currents appear on their correspon...

Страница 5: ...L l2 k2 K L l3 k3 Alarm Relay Generator Input 110 250 V AC C12 C11 C10 C9 C8 C7 C5 C4 C3 C2 C1 C13 C14 C15 C6 RG3 15C CS Current value of 3 Phase fuses which are connected to protect the capacitors mu...

Страница 6: ...tched to the generator operation for any generator starts including the ones for maintaining purposes a b c After the device is energised it finds connection errors and corrects them automatically Pow...

Страница 7: ...the option on is selected in the automatic setup menu the automatic capacitor recognition will start without exiting the menu The step powers which are calculated after this process must always be che...

Страница 8: ...nection option To change this setting press the SET button When Auto connection is on the device controls its connection automatically at start up and corrects any existing measurement input errors If...

Страница 9: ...WN buttons select the Program Prog menu When program menu is displayed program LED turns on SAUE If you want to leave the setup menu without making any other changes press the ESC button until SAVE SE...

Страница 10: ...not press the ESC button Enter a value between 1 1800 seconds and then press SET button Using the UP DOWN buttons enter to another menu option which you wish to change If you are not going to change...

Страница 11: ...PS 10 is selected power value of the first capacitor step is measured and other steps power values are calculated according to selected program Note When setup parameter is selected as on in Auto menu...

Страница 12: ...until SAVE SEt yES shows on the screen If you want to save the changes press the SET button If not press the ESC button When PS 10 Program 10 is selected connection type and capacitor power value sett...

Страница 13: ...Transformer Ratio Setting To obtain accurate power values when calculating the capacitor step powers current and voltage transformer ratios must be entered correctly If these ratios are entered incor...

Страница 14: ...the screen If you want to save the changes press the SET button If not press the ESC button In this menu voltage transformer ratio can be set between 1 2000 For Example For a 34 5 kV 100 V transformer...

Страница 15: ...selected Reset LED turns on Press the SET button to enter reset rESEt setting options Press the SET button to set the alarm ALAr setting which is the first setting in the reset rESEt menu Select yES...

Страница 16: ...arm Setting 3 8 Alarm Settings In this menu overvoltage value is set between 0 300 V for Vtr 1 If this value is set as 0 this function is disabled 3 8 a a Overvoltage Setting SAUE If you want to leave...

Страница 17: ...the overvoltage delay time setting menu SAUE If you want to leave the setup menu without making any other changes press the ESC button until SAVE SEt yES shows on the screen If you want to save the ch...

Страница 18: ...e ESC button SAUE If you want to leave the setup menu without making any other changes press the ESC button until SAVE SEt yES shows on the screen If you want to save the changes press the SET button...

Страница 19: ...erthemenu Using the UP DOWN buttons find the alarm menu ALr When alarm menu is selected alarm LED turns on Press the SET button to enter the alarm ALr settings Using the UP DOWN buttons find over volt...

Страница 20: ...uttons SAUE If you want to leave the setup menu without making any other changes press the ESC button until SAVE SEt yES shows on the screen If you want to save the changes press the SET button If not...

Страница 21: ...the energy values can be entered with 0 1 kWh kVArh precision for both counters Resetting the energy counters can be done from this menu Energy counters can also be conditioned to work with the gener...

Страница 22: ...ut The conditioning of the energy counters is done in this menu There are 2 parameters If the gEn ACt no parameter is selected Energy Counter 1 and Energy Counter 2 will count simultaneously If the gE...

Страница 23: ...ud rate menu bAUd SAUE If you want to leave the setup menu without making any other changes press the ESC button until SAVE SEt yES shows on the screen If you want to save the changes press the SET bu...

Страница 24: ...n be changed and activated in this menu When the password is activated a pin code is always required before entering the menu Thus user password prevents any change to the settings of the device by un...

Страница 25: ...new password press the SET button Enter the new password again and press the SET button If you are going to change another setting return to the menu by pressing the SET button If you do not want to...

Страница 26: ...nics When Cosj values are displayed if DOWN button is pressed Total Inductive Cosj and Total Capacitive Cosj values are observed As you can see in the example below total inductive Cosj value is displ...

Страница 27: ...is phase is export active power Currents I and HAR LEDs on the display indicate that displayed values indicate current harmonic values By pressing the SET button repeatedly THD and odd numbered harmon...

Страница 28: ...are displayed if the DOWN button is pressed inductive reactive and capacitive reactive power values are observed As seen in the example below total reactive inductive power value is displayed on the...

Страница 29: ...import energy and the remaining numbers show the energy value such as 203385706 8 kWh While active import energy is displayed if the DOWN button is pressed active export energy is displayed In the ex...

Страница 30: ...ion Error Compensation Error Defected 1st capacitor step or loads are too variable Target Cosj is capacitive even when all capacitor steps are switched off Capacitor powers are not sufficient for targ...

Страница 31: ...long int unsigned long int long int 0000 0002 0004 0006 0008 000A 000C 000E 0010 0012 0014 0016 0018 001A 001C 001E 0020 0022 0024 0026 0028 002A 002C 002E 0030 0032 0034 0036 0 1 2 3 4 5 6 7 8 9 10...

Страница 32: ...6 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 PHASE 3 VOLTAGE VECTO...

Страница 33: ...00A5 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160...

Страница 34: ...800B 800C 800D 800E 8012 8013 8014 8015 8016 8017 8018 8019 801A 801E 801F 8080 8081 8082 8083 8084 8085 8086 8087 8088 8089 808A 808B 808C 808D 808E 808F 8090 8091 8092 8093 8094 8095 8096 8097 8098...

Страница 35: ...ION 1ST CAPACITOR STEP SWITCH ON OFF 2ND CAPACITOR STEP SWITCH ON OFF 3RD CAPACITOR STEP SWITCH ON OFF 4TH CAPACITOR STEP SWITCH ON OFF 5TH CAPACITOR STEP SWITCH ON OFF 6TH CAPACITOR STEP SWITCH ON OF...

Страница 36: ...R RG3 15C CS CL CLS 35 In the first column total reactive power values of 3 phase capacitors and in second third columns reactive power values of the capacitors in single phase system are shown CAPACI...

Страница 37: ...0 V AC 3 0 s Off 7 0 1 0 s Off 25 15 96 hours 1 1 1 9 600 Kbps no Operating Voltage Un Operating Voltage Range DU Operating Current Range DI Frequency Measurement Class Power Consumption Output Conta...

Отзывы: