When the device is energised for the first time, it checks for connection
errors. If there is a faulty connection, it corrects this fault in itself. In order
for the device to correct a connection fault, 3-phase voltage and current
connections of the device must be done.
NOTE:
If there are other loads than compensation connected to the
system, the device may not find the connection at the first try and may
need several tries. However, if the device is unable to complete the
automatic connection process step calculation process shouldnt be
done.
In order for the calculated capacitor powers to be accurate, the
current and voltage transformer ratios have to be entered correctly
before the automatic capacitor recognition process. If these ratios are
not entered by the user, they will be set as 1 by the device and the
capacitor step powers will be calculated according to these values(Refer
to page 12-CT and VT Ratio Settings).
After any connection faults are corrected by the device; if Auto Setup
option is set as
on
, the device calculates the capacitor step powers
according to the selected program. If 10th program(P-10) is selected , all
of the capacitor step powers are measured seperately. If any other program
is selected, the device measures only the first capacitor step power and
then calculates the other step powers according to the selected
program
(Refer to page 7-Step Number Setting).
NOTE: If the option on is selected in the automatic setup menu, the
automatic capacitor recognition will start without exiting the menu.
The step powers which are calculated after this process must always
be checked.
Inductive load step powers cant be calculated automatically for RG3-
15CL/CLS. Power values have to be entered manually.
Press
UP
or
DOWN
button
to select.
POWER FACTOR CONTROLLER
RG3-15C/CS/CL/CLS
3.1.b Automatic Capacitor Recognition Mode Setting
6
Press the SET button for 3 s in order to enter the menu.
Select
on
or
of
using the
UP
and
DOWN
buttons(Select
on
for automatic
capacitor recognition).
Press
SET
button to set the parameters in Auto menu option.
To select the automatic operating mode, choose
on
with
UP
or
DOWN
buttons and press
SET
button. To select the manual
operating mode, choose
oF
with
UP
or
DOWN
buttons and
press
SET
button.
The first setting in this menu is the operation mode(Operati). The
operation mode of the device is selected according to this options
on or off selection. Press
SET
button to change this setting.
In Auto Operatý menu, choose Auto Setup menu by pressing
the
UP
button.
The 2nd setting in this menu is the Auto Setup setting. The
automatic setup will or will not start according the options on
or off selection. To change this setting, press the SET button.
Numerical values of the parameters are set via buttons in
the display. The blinking digit indicates which digit will be
set. Numerical value of the related digit is increased or
decreased via
UP
or
DOWN
button. To set the next
digit,
SET
button is used. To go back to the previous
digit,
ESC
button is used.