Entek IRD 6652 DSP Protection Monitor
Configuration
COMM’S submenu
The COMM’S submenu has the following options:
RANGES submenu
The RANGES submenu has the following options:
BAUD
PARITY
RESCALE
SCALE
EXIT
MODULE
SET
Factory menu
→
COMM’S
MODULE
Choose the MODBUS serial address for the monitor (1–247). The address
must be unique in the MODBUS network.
BAUD
Choose the speed for serial communications (4800, 9600, 19200, 38400).
PARITY
Choose the parity for serial communications (NONE, EVEN).
RESCALE
Choose the format for data transmission (NO, 16 BIT). Some MODBUS
masters handle data as integer numbers, not floating point format. NO uses
floating point format, while 16 BIT uses integer (unsigned) format.
SCALE
Choose the scale for 16 BIT data transmission (0–65535) if the MODBUS
master uses integer (16 BIT) numbers. This sets the value to transmit for
full scale amplitude. Use the same scale factor as the MODBUS master.
EXIT
Return to the Factory menu. The monitor remembers the current values for
menu options, but does not write them to memory until you exit the
Factory menu.
RANGE1
RANGE2
ECCNTRY
EXIT
SPD BND
SET
Factory menu
→
RANGES
SPD BND
Display the submenu for the speed band options. This submenu allows
you to set up to 7 speed bands for alarms.
RANGE1
Display the submenu for transducer and display settings for input
channel 1.
RANGE2
Display the submenu for transducer and display settings for input
channel 2.
ECCNTRY
Display the submenu for the vector (eccentricity) alarm relay action and
the speed band for vector (eccentricity) alarms.
EXIT
Return to the Factory menu. The monitor remembers the current values for
menu options, but does not write them to memory until you exit the
Factory menu.