Installation
Entek IRD 6652 DSP Protection Monitor
11
The relay contacts on the backplane of the 6652 DSP are:
Note:
If you are using the second danger alarm relays for vector (eccentricity) monitoring, the
relay assignments change to the following:
The second alarm relay function is controlled by the MON ECC option in the ECCNTRY
submenu. If you set MON ECC to +RELAY, the monitor uses the second Danger alarm
relay for vector monitoring. See “ECCNTRY submenu” on page 30, and “Understanding
Vector Monitoring” on page 36.
Function
Relay
Function
Relays
Function
Relays
System OK
1
Chan 1 Alert
2
Chan 2 Alert
5
Chan 1 Danger
3 and 4
Chan 2 Danger
6 and 7
Function
Relay
Function
Relays
Function
Relays
System OK
1
Chan 1 Alert
2
Chan 2 Alert
5
Chan 1 Danger
3
Chan 2 Danger
6
Chan 1 Ecc.
4
Chan 2 Ecc.
7