Configuration
Entek IRD 6652 DSP Protection Monitor
13
Configuration
This section describes how you configure the 6652 DSP. All the controls to configure a
6600 monitor are on the front panel of the monitor. There are no jumpers or DIP switches
that you must set to configure the monitor. The 6652 DSP has two levels of configuration:
l
User menu -
This menu allows you to set the date and time, set the Alert and Danger
alarm setpoints, inhibit the Danger alarm relays, and choose the vector monitoring
reference vectors and Danger alarm setpoints.
l
Factory menu -
This allows you to configure all the other parameters, including
MODBUS communications, transducer and tachometer input, display scaling, start-up
multiplier, band pass filters, vector monitoring, speed bands, noise floor, transducer
checks, alarm relay operation, number of channels, and analysis functions.
General Configuration Instructions
All the configuration menus function in the same way. In short, the steps are:
1.
Press and hold two buttons to display the desired menu.
l
For the User menu, press and hold the two
Arrow
buttons until the menu appears.
l
For the Factory menu, press and hold the
Down Arrow
and
SEL
buttons until the
menu appears.
2.
Use the
Arrow
buttons to highlight the desired option.
3.
Press the
SEL
button to display the screen where you change the value for the option.
4.
Use the
Arrow
buttons to change the value.
5.
Press the
SEL
button to return to the menu. For both the User and Factory menus, the
monitor remembers any changes you make, but does not write them to memory until
you exit the User or Factory menu.
Note:
If the current value does not change when you press the
Arrow
buttons (step 4), then the
monitor is protected by the link security feature. Contact your Supervisor for assistance. For
more information on the link security feature, refer to the manual on 6600 monitor
installation, or contact Entek IRD Customer Support.
Below is an example of these steps, describing the process to change the Alert setpoint for
channel 1 of the monitor. You use similar steps to change the value for any of the options in
a menu.
1.
Press and hold the two
Arrow
buttons to display the User menu. Note that the first
option of the menu is highlighted. This means it appears in green text on a black
background (inverse video) on the monitor display.
Use the
Up Arrow
or
Down Arrow
button to move the highlight to ALARMS. Press
the
SEL
button to select the ALARMS option.
INHIB 1
INHIB 2
ECCNTRY
EXIT
SET
ALARMS
CLOCK