Section 40
00-02-0787
2015-03-23
~ 28 ~
S-#
Description
S41
SENDER TYPES: (S41 is only visible if S38=Mechanical.)
This set point allows you to select between Murphy-resistive sending
units or VDO-resistive sending units for Pressure and Temperature
senders.
Factory set to MURPHY
.
S42
START DLY: Set this delay on engine start to the number of seconds
that the start signal must be present before the controller accepts it
and initiates an auto start sequence (adjustable from 1 to 9,999
seconds).
Factory set to 1.
S43
PRESTART DLY: The time the prestart output is turned ON prior to
cranking the engine (adjustable from 1 to 9,999 seconds).
Factory
set to 1.
S44
STOP DLY: Set this delay on engine stop to the number of seconds
that the stop signal must be present before the controller accepts it
and initiates a stop sequence (adjustable from 1 to 9,999 seconds).
Factory set to 1.
S45
START PSI: (S45 is only visible if S35 = Transducer & S37 =
Pressure.) When “pressure” is selected in the start / stop type, an auto
start will occur when the discharge pressure drops to this set point.
(adjustable from 0 to 1000 PSI)
Factory set to 40.
S46
STOP PSI: (S46 is only visible if S35 = Transducer & S37 =
Pressure.) When “pressure” is selected in the start / stop type, an auto
stop will occur when the discharge pressure rises to this set point.
(adjustable from 0 to 1000 PSI)
Factory set to 60.
S47
MAINTAIN PSI: (S47 is only visible if S35 = Transducer & S37 =
Pressure.) When “pressure” is selected in the throttle type, the engine
will be throttled between the “minimum” and “maximum” rpm set
points to maintain this pressure. (adjustable from 0 to 1000 PSI)
Factory set to 50.
S48
DEADBAND PSI: (S45 is only visible if S35 = Transducer & S37 =
Pressure.) When
PRESSURE
is selected in the throttle type, no
throttling will occur while the pressure is in the deadband. This set
point extends above and below the maintain set point (adjustable from
0 to 50 PSI).
Factory set to 2.
Содержание Murphy EMS PRO LITE
Страница 4: ......
Страница 8: ...NOTES ...
Страница 22: ...Section 40 00 02 0787 2015 03 23 14 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 60: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 61: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 62: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 63: ......