Section 40
00-02-0787
2015-03-23
~ 25 ~
S-#
Description
S19
COOLDOWN DLY: You can adjust this variable to the number of
seconds you wish to cool down your engine before it shuts OFF after
a stop signal is received (adjustable from 1 to 9,999 seconds).
Factory set to 180.
S20
CRANK TIME: Set this delay to the desired amount of time you want
each engine-cranking attempt to last. Consult your engine manual for
recommended cranking and resting times (adjustable from 1 to 30
seconds).
Factory set to 10.
S21
REST TIME: Set this delay to the desired amount of time you want
each rest period between cranking attempts to last. Consult your
engine manual for recommended resting and cranking times
(adjustable from 1 to 30 seconds).
Factory set to 10.
S22
RECRANK DELAY: This delay is used to adjust the amount of time
the controller will wait for the engine to stop moving before attempting
another crank if a false start occurs. During a false start, the engine
starts but then dies before the LOCKOUT DELAY (S9) has expired
(adjustable from 1 to 30 seconds).
Factory set to 10.
S23
CRANK STOP RPM: This RPM set point is used to adjust where the
controller releases the starter during cranking. Set this to the RPM the
engine attains just as it starts. Set this way, the starter is not
unnecessarily engaged after the engine starts. This is how the
controller senses whether the engine is running or not.
Factory set to
300.
S24
CRANK ATTEMPTS: Set the number of attempts you would like the
controller to try an engine start. If the engine fails to start after the
number of attempts you have selected, it will fail and display
OVERCRANK on the front display. This shutdown requires a manual
reset.
Factory set to 6.
S25
WARMUP RPM: This is the engine RPM the controller will throttle the
engine to during warm-up in auto mode. Consult the engine manual
for the optimum warm-up speed. (adjustable from 1 to 9,999 seconds)
Factory set to 600.
S26
COOLDOWN RPM: This is the engine RPM the controller will throttle
the engine to during cooldown. Consult the engine manual for the
optimum cooldown speed.
Factory set to 600.
S27
MIN ENG RPM: When throttling in the AT LOAD state, the engine will
not throttle below this set point.
Factory set to 750.
Содержание Murphy EMS PRO LITE
Страница 4: ......
Страница 8: ...NOTES ...
Страница 22: ...Section 40 00 02 0787 2015 03 23 14 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 60: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 61: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 62: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 63: ......