Section 40
00-02-0787
2015-03-23
~ 17 ~
NOTE
:
OVERCRANK
If the engine fails to start after the number of cranking
attempts is exceeded, OVERCRANK will be indicated on the
display. The auto start sequence will be stopped, requiring
manual reset of the controller. The controller is reset by
moving the panel key switch to the "OFF" position.
•
When the engine speed rises above the crank stop set point, the
following will occur:
The STATE: text line will display “WARMUP”
The “warm-up delay” begins timing
The crank output is turned OFF
The prestart output is turned OFF
The internal hourmeter begins recording engine run hours
The engine is throttled to the “WARMUP RPM” set point
NOTE
: When you set the Engine Type, if you selected
Mechanical
, the throttle actuator will throttle the engine. If you
set
Electronic
, the ECU throttling is determined by what you
selected in the ECU
THROTTLE TYPE
.
The “shutdown lockout” delay begins timing. When this delay
expires, the following shutdowns are armed:
-
Low Oil Pressure
-
High Engine Temperature
-
Loss of Speed
-
ALT Fail/Low Bat
NOTES
If the engine speed drops below the “crank stop” set point
before the “shutdown lockout” delay expires, the “re-crank”
delay begins timing. When this delay expires, cycle cranking
will resume.
If the engine speed drops below the “crank stop” set point
after the “shutdown lockout” delay expires, the engine will be
shutdown on LOSS OF SPEED.
Содержание Murphy EMS PRO LITE
Страница 4: ......
Страница 8: ...NOTES ...
Страница 22: ...Section 40 00 02 0787 2015 03 23 14 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 60: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 61: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 62: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 63: ......