Section 40
00-02-0787
2015-03-23
~ 12 ~
If you are using the
EMS PRO LITE
on an Interim Tier 4 engine, please
read and understand the information for the following S-numbers: S73,
S74, and S75 in the S-number table, page 22. Also, read and understand
the following information and steps to set up Tier 4 Emission options.
The controller displays the SOOT level on the display when the engine
has been de-rated and/or when regeneration (regen) is required to return
to normal service. You must set S73 (Tier Rating) to
Tier 4
for these
options to be available.
•
If S74 (Tier State) is set to Auto DPF Regen, the ECU
performs a regen automatically. This only occurs if the
ECU conditions allow.
•
If S75 (Request DPF Regen) is set to YES, the controller
commands the ECU to perform a regen. This only occurs
if ECU conditions allow.
•
If S75 (Request DPF Regen) is set to NO, Inhibit Regen is
active and no regen occurs.
To use the controller on a Tier 4 engine, follow the steps below:
1.
Access the S Menu by pressing
[Menu]
.
2.
Press the
[Up or Down Arrow]
to scroll to the correct
Entry Code (See Entry Code Supplement for Entry
Codes).
3.
Press the
[Up or Down Arrow]
until S73 (Tier Rating)
is displayed in the menu and press
[Enter]
.
4.
Press the
[Up or Down Arrow]
until TIER 4 is
highlighted and press
[Enter]
.
5.
Press the
[Up or Down Arrow]
until S74 (Tier State)
is highlighted and press
[Enter]
. The default value is
set to INHIBIT. To select
Auto DPF Regen
use the
[Up or Down Arrow]
to highlight the text and press
[Enter]
.
To use the Request DPF Regen feature, follow these steps (If all the
conditions for a regen to occur are not met, this request could be ignored
by the ECU):
1.
Access the S Menu by pressing
[Menu]
2.
Press the
[Up or Down Arrow]
and scroll to the
correct Entry Code (See Entry Code Supplement for
Entry Codes).
3.
Press the
[Up or Down Arrow]
until S75 (Request
DPF Regen) is displayed in the menu and press
[Enter]
.
4.
Press the
[Up Arrow]
until YES is highlighted and
press
[Enter]
.
Содержание Murphy EMS PRO LITE