4. Installation

Each monobloc is supplied with the terminal/connector fasteners.
On each monobloc the positive terminal is identified by a “+” symbol. Install 
the batteries in accordance with the instructions and/or layout drawing, 
taking care to ensure correct terminal location and polarity.
Connect the blocs with the connectors and fasteners provided. The fastener 
torque value is indicated on the product label.
Place the insulating covers in position immediately after tightening the 
fasteners.

5. Operation

5.1. Standby / Float Operation

Constant voltage chargers are recommended. The charging voltage should 
be set at the equivalent of 2.29Vpc at 20°C/68°F or 2.27Vpc at 25°C/77°F. 
The minimum charging voltage, at any temperature, is 2.21Vpc. The 
recommended float voltage temperature compensation is as follows:

Disconnecting the battery from the load when the recommended end 
voltage is reached will eliminate the risk of over-discharge. We recommend 
that the charge voltage is reapplied within 24 hours, up to a maximum of 7 
days, of any discharge.

5.2. Charging Current

Due to the very low internal resistance PowerSafe

®

 V-FT monoblocs will 

accept unlimited current during recharge but for cost and practial purposes 
in float applications where recharge time to repeat duty is not critical, the 
rectifier current can be limited to the load plus 0.1C

10

 Amps.

5.3. Grid Assist Cycling Applications

In instances where the time time to repeat duty is critical the charge voltage 
should be set to 2.40Vpc at 20°C, with the rectifier current limit set to a 
minimum of 0.1C

10

 A. Fast charge should be stopped and reverted to float 

voltage once full state of charge is reached.

5.4. Periodic Boost Charge

In normal operation a periodic boost charge is not required. However, in 
some cases such as when there has been no discharge duty over a 12 
month period, a boost charge equivalent to 2.40Vpc at 20°C for maximum of 
10 hours can be applied.

6. Maintenance

In practice, the user usually specifies the maintenance schedule based on 
site criticality, location and manpower.
However, the following may be used as a suggested maintenance schedule.

• 

Monthly (record all readings)

Measure the battery string voltage. If necessary, adjust the float voltage 
to the correct value.

• 

Every six months (record all readings)

Measure the battery string voltage. If necessary, adjust the float voltage 
to the correct value.

Measure individual bloc/cell voltages. The blocs/cells should be within 5% of 
the average.

Inspect for contamination by dust, lose or corroded connections.
If necessary, isolate the string/bloc/cell and clean with a damp soft cloth. 
Warning: Do NOT use any type of oil, solvent, detergent, petroleum-based 
solvent or ammonia solution to clean the battery containers or lids. These 
materials will cause permanent damage to the battery container and lid and 
will invalidate the warranty.

Contact EnerSys

®

 if you have any questions regarding maintenance.

7. Disposal

PowerSafe V-FT batteries are recyclable. Scrap batteries must be packaged 
and transported in accordance with prevailing transportation rules and 
regulations.

Scrap batteries must be disposed of in compliance with local and national 
laws by a licensed or certified lead acid battery recycler.

Temperature (°C / °F)

10/50

15/59

20/68

25/77

30/86

35/95

40/104

Recommended

2.33

2.31

2.29

2.27

2.25

2.23

2.21

Minimum

2.31

2.29

2.27

2.25

2.23

2.21

2.21

Содержание PowerSafe V-FT

Страница 1: ...aintenance Manual Manuel d installation d exploitation et de maintenance Manual de Instalaci n funcionamiento y mantenimiento Manual til indbygning drift og vedligeholdelse Asennus k ytt ja huolto ohj...

Страница 2: ...2 29 2 40Vpc with 10 of the C10 current available for a period of 24 hours 2 3 Commissioning Charge Before commencing operation the battery must be given a commissioning charge The batteries should b...

Страница 3: ...be stopped and reverted to float voltage once full state of charge is reached 5 4 Periodic Boost Charge In normal operation a periodic boost charge is not required However in some cases such as when t...

Страница 4: ...ation lorsque le bloc atteint l quivalent de 2 10 volts par l ment Vpc ou une fois la dur e de stockage maximale atteinte ceci selon l ch ance survenue la premi re 2 2 Charge d galisation Charger les...

Страница 5: ...leinement charg e 5 4 Charge intensive p riodique En service normal une charge intensive p riodique n est pas n cessaire Dans certains cas toutefois lorsqu il n y a pas de d charge en service sur une...

Страница 6: ...funcionamiento la bater a debe recibir una carga de puesta en servicio Las bater as deben cargarse utilizando tensi n constante con una corriente de carga m nima de 0 1 C10 sin carga conectada a la b...

Страница 7: ...un m nimo de 0 1 C10 A Debe detenerse la carga r pida y revertirse a tensi n de flotaci n una vez se alcance el estado de carga completa 5 4 Carga r pida peri dica En el funcionamiento normal no es n...

Страница 8: ...V FT P 1 1 1 EnerSys 1 2 EnerSys EnerSys 2 2 1 2 10 2 2 2 29 2 40 10 C10 24 2 3 0 1C10 7 2 29 20 C 24 2 40 20 C 24 60 C 8 65 C F 10 50 48 12 15 59 34 12 20 68 24 12 25 77 17 6 30 86 12 6 35 95 8 5 3...

Страница 9: ...25 C 77 F 2 21 24 7 5 2 PowerSafe V FT 0 1 C10 5 3 2 40 20 C 0 1C10 5 4 12 2 40 20 C 10 6 5 EnerSys 7 PowerSafeV FT C F 10 50 15 59 20 68 25 77 30 86 35 95 40 104 2 33 2 31 2 29 2 27 2 25 2 23 2 21 2...

Страница 10: ...ilslutninger skal tages af og l gges v k Rygning og ben ild er forbudt undg gnister Beskyt jnene L s vejledning igennem Fare som f lge af elektrisk st d Fare Genanvend gamle batterier Batterier indeho...

Страница 11: ...n indstilles til 2 40 V pr celle ved 20 C under begr nsning af ensretterstr mmen til et minimum p 0 1 C10 A S snart batteriet er fuld opladt b r lynopladningen stoppes hvorefter der skal vendes tilbag...

Страница 12: ...ennen kapasiteetti tai kuormituskokeen tekemist Akut on ladattava vakioj nnitteell ja 0 1 C10 n v himm islatausvirralla niin ettei akkuun ole kytketty kuormitusta Lataus voidaan tehd jommalla kummalla...

Страница 13: ...int n 0 1xC10 A Kun t ysi varaus on saavutettu on pikavaraus lopetettava ja tasasuuntaaja kytkett v kestovarausj nnitteelle 5 4 S nn llinen virkistysvaraus Normaalissa k yt ss s nn llist virkistysvara...

Страница 14: ...14...

Страница 15: ...15...

Страница 16: ...18 6300 Zug Switzerland EnerSys Asia 152 Beach Road Gateway East Building 11 03 Singapore 189721 Tel 65 6508 1780 2016 EnerSys All rights reserved Trademarks and logos are the property of EnerSys and...

Отзывы: