background image

 

 

Mojave

 Grid-Hybrid 

Energy Storage System

 

 

 

 

 

Operator’s Manual 

 

Содержание OutBack POWER Mojave

Страница 1: ...Mojave Grid Hybrid Energy Storage System Operator s Manual...

Страница 2: ...w outbackpower com Warranty The warranty for this product can be downloaded from www outbackpower com downloads warranty_and_safety warranty_mojave A printed copy is available by sending a self addres...

Страница 3: ...17 Grid Tab 18 Generator Tab 19 Network Tab 21 ACTIONS View 22 SETTINGS View 23 EVENTS View 24 OPTICS RE 25 Operation 27 Connections 27 CT 27 LED Indicator Inverter 28 Description of Inverter Operatio...

Страница 4: ...oting 70 Service Instructions 71 Replacement Kits 71 Preparatory Steps 72 Replacement of Control Board 74 Replacement of AC Board 77 Replacement of Fan Module 81 Replacement of Power Module 82 Replace...

Страница 5: ...ule 21 91 Table 16 Grid Protection Settings HECO and ISO NE 94 List of Figures Figure 1 Mojave Inverter Charger and Battery 9 Figure 2 User Interface 11 Figure 3 User Interface Tabs and Views 12 Figur...

Страница 6: ...33 Cover Replacement 61 Figure 34 Measurement Points 64 Figure 35 Removal of Covers 73 Figure 36 Control Board External Attachments 74 Figure 37 Control Board Connectors 75 Figure 38 Dismounting Cont...

Страница 7: ...he hazard could be harmful to human life CAUTION Hazard to Equipment This type of notation indicates that the hazard may cause damage to the equipment IMPORTANT This type of notation indicates that th...

Страница 8: ...ad all instructions The instructions indicated here include this manual as well as the Mojave BatteryQuick Start Guide and any other pertinent literature AVERTISSEMENT Pour pr venir les blessures lire...

Страница 9: ...igned to be AC Coupled that is the ESS is meant to be installed in existing grid direct systems to add energy storage and backup capability without interfering with grid interaction The system has an...

Страница 10: ...in the event of low batteries or other conditions Listed by UL to UL 1741 2nd Edition with supplements SA and SB and CSA 22 2 107 1 16 Meets SunSpec IEEE 2030 5 2018 CSIP Provides secure communication...

Страница 11: ...ill appear after power up It appears as Mojave xxxx and incorporates part of the inverter s serial number Connect to the device When prompted for a wi fi password the password consists of the last eig...

Страница 12: ...ection Selecting an individual tab brings up a table with data See page 13 for more information on this view and each tab The SETTINGS view allows functions to be changed Selecting an individual tab b...

Страница 13: ...n of power flow This is also shown by a chevron style arrow at the destination icon A green dotted line indicates power not purchased from grid or generator During AC coupled operation see page 35 the...

Страница 14: ...Disconnected if the grid relay is automatically opened for another reason while grid power is still present Inverter The Mojave inverter itself See page 16 for more information including all Status i...

Страница 15: ...erator The AC source on the inverter s GEN terminals This icon displays generator voltage and frequency See page 19 Icon colors Green generator Status is Connected Inverter is using generator power Th...

Страница 16: ...e L1 The voltage in AC volts Vac measured at the inverter s L1 LOAD terminal Voltage L2 The voltage in AC volts Vac measured at the inverter s L2 LOAD terminal Current L1 The current in AC amperes Aac...

Страница 17: ...age in DC volts Vdc measured at the inverter s internal battery terminals Current The net current in DC amperes Adc measured as imported or exported from the batteries Temperature The battery temperat...

Страница 18: ...watts W measured at the external current transducers This will read zero if the transducers are disabled See pages 27 and 39 XCT Current L1 and XCT Current L2 The current in AC amperes Aac measured a...

Страница 19: ...nting the generator s running time Disconnected voltage is present at the GEN terminals but the power is unacceptable or was manually disconnected The generator relay is open Cooling Down generator is...

Страница 20: ...ab See pages 22 and 46 It is waiting for proper conditions to start the generator Disabled The AGS function has been been deactivated in the Actions Menu in the Generator tab or both The generator may...

Страница 21: ...refers to the system s router Wired The connection state when using a wired cable network connection Disabled The configuration has manually disabled the connection Disconnected The wireless interface...

Страница 22: ...ct or Drop disconnect This is a manual command to connect or disconnect from the utility grid Use connects to the grid if all other conditions are met See page 41 F Gen Input This onscreen toggle has...

Страница 23: ...of each setting The tabs may appear in a different order in Operation than they do here Inverter Allows settings for all inverter functions including Time of Use ToU See page 33 Grid Allows settings...

Страница 24: ...ion on a status change or other event Warning a non critical issue that does not require the unit to shut down Fault a critical wiring related issue that requires the unit to shut down Error a critica...

Страница 25: ...alled OutBack Power equipment Each inverter is treated as a different System A video tutorial for aggregating multiple Systems with OPTICS RE is part of the WattSchool series of tutorials OPTICS RE al...

Страница 26: ...PTICS RE Note that the following steps require a valid MAC address from page Error Bookmark not defined 2 Click on Add a Profile 3 Set the System Type as Mojave 4 Enter the MAC address for a Mojave in...

Страница 27: ...46 Each distinct function or operation is accompanied by a symbol representing the inverter and that operation as shown in Figure 14 Figure 14 Icon Images CT Normally the Mojave inverter senses AC pow...

Страница 28: ...blue during a firmware update Solid Ready for operation The Mojave inverter is off Green Solid The Mojave inverter is operating Any number of functions may be active See page 13 Yellow Flashing An er...

Страница 29: ...can be manually selected enabled or customized Other items are general topics or applications for the inverter Any of these items may need to be adjusted so that the inverter is best matched to a par...

Страница 30: ...Owner settings allow changes to items under the Network Inverter Battery or Generator tabs The Installer settings can change the grid protection settings under the Grid tab The Admin selection is rese...

Страница 31: ...st or forgotten press the Reset button to reset the password Additional instructions will appear Historical Data This item allows download of a csv file to review system data Enter the date range unde...

Страница 32: ...l auto populate this item DNS server 1 and 2 The first and second domain name servers DHCP will auto populate these items If a static network is used these items are available from the service provide...

Страница 33: ...fect the voltage transferred from an AC source See pages 34 41 and 48 Inverter Operating Frequency Hz Range 55 to 66 Default 60 In off grid usage the inverter s operating frequency can be adjusted for...

Страница 34: ...ng 35 Aac will be current limited similar to an excessive load and may result in undervoltage The Mojave ESS requires the Mojave Lithium Ion Battery for normal operation No other DC sources are suppor...

Страница 35: ...activity the GD inverter sends power to F and C The inverter s first priority is to charge the batteries D The Mojave battery charger settings will still apply See page 44 If additional GD power is a...

Страница 36: ...is preset to operate between 4 PM and 9 PM as this is the most common peak rate period Weekends utilizes ToU during this time block Saturday and Sunday only Daily utilizes ToU during this time block e...

Страница 37: ...acting as a conduit for the GD inverter to export power At 5 PM the inverter enters the peak rate period The Mojave inverter ceases importing any grid power By this time the GD inverter is producing...

Страница 38: ...e inverter If a rapid shutdown device is not installed this function should be disabled This is performed by directly shorting terminals 5 and 6 with a small wire A jumper is installed at the factory...

Страница 39: ...nterconnection Not all items are available with all Grid Profiles The settings shown are for the IEEE 1547 2003 profile Certified ranges are only shown when they differ from the maximum range IMPORTAN...

Страница 40: ...Hz Range 55 to 66 Default 59 50 Enter service delay s Range 0 to 1600 Default 300 Random delay s Range 0 to 1000 Default 0 Enter service ramp time s Range 0 to 1000 Default 300 PF export Range Disabl...

Страница 41: ...me settings under the Inverter tab SETTINGS view The inverter will restrict charging from the grid if any of the following conditions are true Charge from grid limit W is set to a low number Max charg...

Страница 42: ...d power to the GEN terminals NOTES The relay does not open during any stage of Time of Use See page 36 The neutral connections are not switched Neutral conductors use a common bus bar The independent...

Страница 43: ...mport limit W the charge rate will be reduced to zero If the loads exceed Import limit W see below The Charge from grid limit W setting does not restrict charging performed while AC coupling See page...

Страница 44: ...d for the Mojave ESS Max SOC Range 60 to 100 Default 100 The uppermost SOC for the charger to work See page Error Bookmark not defined Min SOC Range 10 to 60 Default 50 The lowest operating point for...

Страница 45: ...djust the charging voltage and current to maintain the best performance of the battery while still respecting any user set limits There is no typical BMS charging cycle due to the adaptive nature for...

Страница 46: ...erator is allowed to run with no load before charging begins This time should follow the generator manufacturer s recommendations This setting applies only when using AGS See pages 48 and 50 Cooldown...

Страница 47: ...atically during certain hours See page 53 Quiet time start Range 12 00 AM to 11 59 PM Default 10 00 PM The beginning of the scheduled period that restricts automatic start See page 53 Quiet time stop...

Страница 48: ...onnected to other locations The inverter has a separate GRID connection see page 42 These independent connections are used for wiring to multiple AC sources However the inverter can only use one AC so...

Страница 49: ...D When the relay closes the GEN and LOAD terminals are electrically common The GRID terminals remain isolated When the relay changes states the physical transfer delay is as fast as 20 milliseconds Th...

Страница 50: ...ator with a three wire start circuit a three wire to two wire conversion kit may be needed in conjunction with the AUX Atkinson Electronics www atkinsonelectronics com is one company that makes these...

Страница 51: ...rator automatically The advanced functions allow generator control based on battery state or load size It can be exercised during inactive periods or prevented from starting late at night or during ot...

Страница 52: ...See page 16 NOTE When using the Mojave Lithium Ion Battery which uses BMS to determine SoC this is the most advisable mode to use Voltage Start When the batteries discharge to any of several selected...

Страница 53: ...es when generator noise is not desired the generator can be prevented from starting automatically The 24 hour and 2 hour start settings will not start the generator during these times Similarly the St...

Страница 54: ...Cycle Stop Reasons Stop SOC Below Stop kW Quiet Time Exercise Time Expires Generator set to Off Generator Controls Run During Quiet Time 2 minute start voltage Yes Stop Stop Stop Yes 2 hour start volt...

Страница 55: ...ed or disconnected to avoid causing a spark CAUTION Equipment Damage Failure to install or use this product as instructed can result in damage to the product that may not be covered under the limited...

Страница 56: ...and or flammable gas must be installed on the site in accordance with building fire and installation codes Ventilation Room must not be sealed airflow to the outside is required Use of an exhaust fan...

Страница 57: ...are provided in the hardware kit Install these bumpers into the rear of the battery by pushing them into the holes designated by D in Figure 29 Figure 29 Rubber Bumpers A C B o Circuit Breaker A This...

Страница 58: ...ackets E into the top slots on the battery as shown in the Figure 30 inset These brackets will sit loosely until secured in the next step 4 Two lag screws of 1 4 thickness F are provided in the hardwa...

Страница 59: ...r wiring access To open the wiring compartment use a 5 mm hex Allen driver to remove the four M6 screws holding the cover in place G in Figure 31 The following items are included in the hardware kit E...

Страница 60: ...wdriver 5 Tighten all conductors according to Table 3 Table 3 Battery Torque Values Cable In lb Nm Positive I 65 to 75 7 3 to 8 5 Negative H 65 to 75 7 3 to 8 5 Ground J 35 4 0 6 The BMS port is locat...

Страница 61: ...eshooting The battery icon in the STATUS view will turn red at the same time See page 17 See EVENT view on page 24 for further descriptions of any status Battery Use Commissioning To commission the ba...

Страница 62: ...ery s condition and automatically assesses the best charging parameters based on current conditions These parameters can be communicated to the inverter charger using the CANBUS connection There is no...

Страница 63: ...difference between my own handheld meter readings and the readings on the UI Differences in both reading tolerances and calibration may result in different figures In addition efficiency losses are no...

Страница 64: ...rement Points On the following pages Table 5 is organized in order of common symptoms with a series of possible causes It shows which LED indicator or icon colors should accompany a known problem Each...

Страница 65: ...X terminal block Error condition Red LED Various icons red Check the EVENTS view for any errors Will not connect to the AC source Circuit breaker open in wiring compartment Gray source icon grid or ge...

Страница 66: ...ments Low charge rate Charge complete or nearly complete Green battery icon Check the DC voltage and charging stage using the UI Confirm with a handheld DC voltmeter System display DC meter reads sign...

Страница 67: ...hot or neutral output line System neutral and ground may not be bonded N A Using a handheld AC voltmeter test the N L1 and L2 LOAD terminals See page 64 These measurements should give full voltage Tes...

Страница 68: ...o in Action Menu N A Both items must be set before AGS can function In the STATUS view AGS Status will not read Enabled if both items are not set AGS not set to Enable under Generator tab Generator ex...

Страница 69: ...check OPTICS RE for more information To recover the system from this state perform the following steps 1 Verify a charging source AC grid generator etc is available to immediately begin charging the b...

Страница 70: ...battery Battery goes into a fault state red LED and stops providing power during operation Various error states if inverter is powered down UI will not respond Check OPTICS RE for an error log and as...

Страница 71: ...ment kits SPARE 501 Mojave Control Board SPARE 502 Mojave 60 Hz AC Board SPARE 504 Mojave Carrier Board SPARE 506 Mojave Power Module SPARE 508 Mojave Fan Module The instructions for the following kit...

Страница 72: ...nected to the inverter LOAD circuit breaker GRID circuit breaker GEN circuit breaker DC circuit breakers Generator start circuit Voltage Check Once these connections are turned off verify with a voltm...

Страница 73: ...he right Remove the door by pulling inward on the pins C at the corners of the door 6 Inside is a dead front which prevents accidental contact with anything other than the circuit breakers To remove t...

Страница 74: ...the control board SPARE 501 1 Remove the AUX terminal block from its socket See A in Figure 36 Use the black levers B on the sides of the block to help remove it 2 Using a 1 Phillips screwdriver remov...

Страница 75: ...igure 37 SMA connector D for the antenna wire Ribbon cable E for the AC board 5 pin connector F for the current transducer 2 pin connector G for the power modules Figure 37 Control Board Connectors 4...

Страница 76: ...e control board Perform all previous steps in reverse order Insert the control board Replace the screws H Do not tighten Replace the connectors G and F See Figure 37 if necessary Replace the ribbon ca...

Страница 77: ...o the board easier 2 Unclip all wires from AC terminals at the bottom of the board including the neutral wire See B IMPORTANT Mark or note the wire positions so that they can be reinstalled correctly...

Страница 78: ...former terminals See C in Figure 40 IMPORTANT Mark or note the wire positions so that they can be reinstalled correctly The four wires are marked with numbers 5 through 8 They are installed in the pos...

Страница 79: ...00277 01 001 Rev A 79 Service 3 On the AC board remove the following connectors see Figure 41 Ribbon cable D for the control board 2 pin connector E for the transformer Figure 41 AC Board Connectors...

Страница 80: ...he AC board Ensure that the board fits over the two alignment pins H Components on the board can be damaged through mishandling at this stage Replace the screws F Replace the connectors E and D See Fi...

Страница 81: ...ws securing the fan module See C in Figure 43 3 Slide the fan module out of its slot in the direction indicated by D in Figure 43 Note that the module will have to slide under the transformer cables E...

Страница 82: ...ve bolts and washers for transformer cables See C in Figure 45 4 Remove transformer wires by bending them away from work area See D in Figure 45 The voltage sense wires will be completely disconnected...

Страница 83: ...ard guides K See Figure 46 Ensure it is seated firmly Replace bus bars I Replace bolts H Tighten to a torque value of 60 in lb 6 8 Nm See Figure 46 Replace the cage cover by attaching the keyhole fast...

Страница 84: ...or all items Using a 5 mm hex Allen wrench remove the bolts B on the bus bars Using a 5 mm hex Allen wrench remove the bolts C on the bottom of the choke Support the choke while the bolts are being re...

Страница 85: ...ce the carrier board Perform all previous steps in reverse order When reinstalling washers bolts and similar hardware use the replacement hardware included in the kit Replace the carrier board I See F...

Страница 86: ...rcuit breakers before making these checks Battery Maintenance CAUTION Equipment Damage Do not perform any form of equalization with this battery The Mojave ESS battery requires almost no regular maint...

Страница 87: ...bility 30 minute 8 kVA AC Maximum Output Fault Current and Duration 365 Aac for 75 uS AC Maximum Backfeed Current and Duration UL 1741 420 Apeak for 17 7 ms CSA Zero Power Consumption idle Invert mode...

Страница 88: ...ations Table 9 Mechanical Specifications for Mojave Inverter Specification Value Dimensions H W D 37 75 15 87 11 22 95 9 40 3 28 5 cm Packaged Dimensions prone H W L 16 0 21 25 44 5 40 6 53 9 113 0 cm...

Страница 89: ...vironmental Category Indoor unconditioned Wet Locations Classification Wet locations No Relative Humidity Rating 93 Pollution Degree Classification PD 2 Maximum Altitude Rating 6561 2000 m Overvoltage...

Страница 90: ...terconnecting Distributed Resources with Electric Power Systems Directives This product meets the following directive RoHS Directive 2011 65 EU The restriction of the use of certain substances in elec...

Страница 91: ...a n a 5 0 5 0 Volt VAr 1 voltage pu 0 770 1 050 0 770 1 030 n a 0 920 0 920 Volt VAr 1 reactive power pu 0 000 0 700 0 000 0 530 n a 0 440 0 300 Volt VAr 2 voltage pu 0 920 1 050 0 920 1 050 n a 0 980...

Страница 92: ...16 Freq Droop Disabled Enabled n a n a n a Enabled Enabled Freq Droop OF deadband Hz 0 000 1 000 0 000 1 000 n a 0 036 0 036 Freq Droop UF deadband Hz 0 000 1 000 0 017 1 n a 0 036 0 036 Freq Droop OF...

Страница 93: ...setpoint 5 0 400 1 000 0 400 1 000 0 949 1 000 0 950 PF import setpoint 5 0 400 1 000 0 400 1 000 0 949 1 000 0 950 PF export excitation 6 Absorbing Injecting Absorbing Injecting Absorbing Absorbing A...

Страница 94: ...0 0 90 0 n a n a 10 0 10 0 10 0 Volt Watt 1 voltage pu 1 000 1 090 1 000 1 090 1 060 1 060 1 060 Volt Watt 1 power pu 1 000 1 000 1 000 1 000 1 000 1 000 1 000 Volt Watt 2 voltage pu 1 010 1 100 1 01...

Страница 95: ...200 Watt VAr 3 reactive power pu 0 500 0 500 n a n a 0 000 0 000 0 000 Watt VAr 4 power pu 0 000 1 000 n a n a 0 200 0 200 0 200 Watt VAr 4 reactive power pu 0 500 0 500 n a n a 0 000 0 000 0 000 Wat...

Страница 96: ...Absorbing PF import excitation 14 Absorbing Injecting Absorbing Injecting Injecting Injecting Injecting 11 Only one of the four VAr functions Volt VAr Watt VAr Constant PF Constant VAr can be enabled...

Страница 97: ...ew 44 STATUS View 17 BMS 17 Book Symbol 7 C Caution Symbol 7 8 Components 71 CSA 10 90 Current Transducer CT 10 27 39 D Data Download 31 Design 34 E EVENTS View 12 24 F FAQ 63 Firmware Update 31 Funct...

Страница 98: ...ttery 44 Generator 46 Grid 39 Inverter 33 Network 32 SoC 17 Spare Parts 71 Specifications Electrical Inverter 87 Environmental Battery 89 Inverter 89 ESS Shipping 88 Mechanical Battery 88 Inverter 88...

Страница 99: ...900 00277 01 001 Rev A This page intentionally left blank...

Страница 100: ...900 00277 01 001 Rev A Masters of the Off Grid First Choice for the New Grid 3767 Alpha Way Bellingham WA 98226 USA...