You can define up to two peak time periods of the day in the
Maintenance > Relay and Load Shed
screen:
1. In the
Time of Day Action Configuration
dialogue box, set up the start and end time of the first rush hour
under
Time Period 1
and the second rush hour under
Time Period 2
.
In this example, during the first time
period (7 AM to 9 AM), all 3 timers are disabled (they do not count down at all). Similarly, all timers are disabled
during the second time period (3 PM to 6 PM).
2. Select
ON
under each time period. Click the
Update Configuration
button under the time periods to store the
settings.
Figure 30 — Time Of Day Configuration
Figure 31 — Time Of Day Action Status
3. Confirm your settings in the
UPS Monitoring > Relay and Load Shed > Time of Day Action Status
screen.
Once the
Time of Day Action
is configured, the Alpha Micro 100 will automatically disable the timers during the
Inverter mode at the defined peak periods.
You can switch off the
Time of Day Action
by setting one or both time period(s) to
OFF
(Figure 46). The dry contact
will be activated by the timer regardless of the peak period settings.
C3 to C6 are
not available on
the Alpha Micro
100.