Operation via FOUNDATION™ Fieldbus
RID16
54
Hauser
11.3.5
Transducer Block "Advanced Diagnostic"
The Advanced Diagnostic Block informs about the current device status and the last status. As well
it indicates for which channel the current diagnostic event of the value appears.
It contains the minimum and maximum values for each analog channel.
DISP_VALUE_1[...8]_BGMAX:
Enter the maximum (100%) value for bargraph presentation.
DISP_VALUE_1[...8]_PERCENT:
Switch the percent symbol on/off. No recalculation of the displayed value is
done.
DISP_VALUE_1[...8]_SETUP_DIGITAL:
Select a representation of digitals values. This setting is valid once a digital
source is selected.
Availabel parameters are:
• 1 = On; 0 = Off
• 0 = On; 1 = Off
• 1 = Open; 0 = Close
• 0 = Open; 1 = Close
• display as decimal value
Transducer Block “DISPLAY” (E+H parameters)
Parameter
Index
Parameter
Write access with
operating mode
(MODE_BLK)
Description
Transducer Block “ADVANCED DIAGNOSTIC” (E+H parameters)
Parameter
Index
Parameter
Write access with
operating mode
(MODE_BLK)
Description
11
CURRENT_STATUS_
NUMBER
Read only
Shows the current diagnostic and its category.
F = Failure
M = Maintenance
S = Out of Specification
C = Function check
12
CURRENT_STATUS_DESC
Read only
Shows a description to the current message.
13
CURRENT_STATUS_
MAINTENANCE
Read only
Diagnostic number
Description
F437
• Input Selector 1 is not instantiated, but used as
source
• Input Selector 2 is not instantiated, but used as
source
• PID is not instantiated, but used as source
• Arithmetic block is not instantiated, but used as
source
• Integrator block is not instantiated, but used as
source
• Listener mode and source analog is switched on,
switch one off
• Listener mode and source digital is switched on,
switch one off
• Source analog and source digital is switched on,
switch one off
• Listener mode, source analog and source digital is
switched on, switch two off
• Device address for listener mode is not available,
change address to valid publisher