RID16
Operation via FOUNDATION™ Fieldbus
Hauser
51
6
Block Error (BLOCK_ERR)
Read only
The active block errors appear on the display.
Display:
OUT OF SERVICE
The block is in the "out of service" operating mode.
The following block errors are only shown in the Sensor Transducer Blocks:
•
MAINTENANCE NEEDED
The device must be checked since an active device error is pending. The
detailed cause of the error can be called up in the "Advanced Diagnostic"
Transducer Block by means of the "CURRENT_STATUS_CATEGORY" and
"CURRENT_STATUS_NUMBER" parameters.
•
LOST STATIC DATA / LOST_NV_DATA
The memory is inconsistent.
•
POWER-UP:
Status message during the startup procedure.
•
BLOCK CONFIGURATION ERROR:
The block was configured incorrectly.
•
0x0000:
No active block error present.
An exact error description as well as information on rectifying faults can be
found in Section 9.2.
7
Update Event
(UPDATE_EVT)
AUTO - OOS
Indicates whether static block data have been altered, including date and time.
8
Block Alarm
(BLOCK_ALM)
AUTO - OOS
The current block status appears on the display with information on pending
configuration, hardware or system errors, including information on the alarm
period (date, time) when the error occurred.
!
Note!
• In addition, the active block alarm can be acknowledged in this parameter
group.
• The device does not use this parameter to display a process alarm since this is
generated in the BLOCK_ALM parameter of the Analog Input function
block.
9
Transducer Type
(TRANSDUCER_TYPE)
Read only
The Transducer Block type appears on the display.
Display:
• Display Transducer Block: Custom Display
Transducer
• Advanced Diagnostic Block: Custom Adv. Diag.
Transducer
10
Transducer Error
(XD_ERROR)
Read only
The active device error appears on the display.
Possible display:
• No Error (normal status)
• Electronics failure
• Data Integrity Error
• Mechanical failure
• Configuration Error
• Calibration error
• General Error
!
Note!
Summarized device status/condition, more precise
information on the pending error(s) is available by
means of the manufacturer-specific error display. This
can be read via the Transducer Block “Advanced
Diagnostic” in the “CURRENT_STATUS_CATEGORY”
and "CURRENT_STATUS_NUMBER" parameters.
An exact error description as well as information on
rectifying faults can be found in Section 9.2.
Transducer Block (FF parameters)
Parameter
Index
Parameter
Write access with
operating mode
(MODE_BLK)
Description