Wiring

RID16

10

Hauser

4

Wiring

"

Caution! 
• Switch off power supply before installing or connecting the device. Failure to observe this may 

result in destruction of parts of the electronics.

• When installing Ex-approved devices in a hazardous area please take special note of the 

instructions and connection schematics in the respective Ex documentation added to these 
Operating Instructions. The local E+H representative is available for assistance if required.

• The 4-pin post connector is only designed for connecting the associated display. Connecting other 

devices can destroy parts of the electronics.

Devices can be connected to the FOUNDATION Fieldbus™ in two ways:

• Connection via conventional cable gland

Chap. 4.2.1

• Connection via fieldbus connector (optional, can be purchased as an accessory) 

Chap. 4.2.2

4.1

Connecting the cable to the field indicator

4.1.1

Mounting the cable gland or fieldbus connector in the plastic 
housing

Firstly, open one of the knock-outs provided on the bottom of the housing. Use a suitable tool, e.g. 
a screwdriver.

"

Caution! 
Open the knock-out at room temperature. At very low temperature the housing might be damaged.

a0012980

Fig. 5: 

Opening a knock-out on the bottom of the field indicator

Proceed as follows for mounting (

å

7):

1.

Open the housing front of the field housing.

a0011636

Fig. 6: 

Opening the housing of the field indicator

1

internal grounding terminal (only aluminum housing)

Содержание RID16

Страница 1: ...BA284R 09 en 02 10 71092450 Operating Instructions RID16 Field Indicator with FOUNDATION Fieldbus protocol 9...

Страница 2: ...operating elements 20 Information on configuration and operating programs from other manufacturers Information about setting the hardware write protection device address etc for FOUNDATION Fieldbus c...

Страница 3: ...protection 18 4 5 Post connection check 18 5 Operating the field indicator 19 5 1 Quick operation guide 19 5 2 Display and operating elements 20 5 3 FOUNDATION Fieldbus technology 20 5 4 Configuration...

Страница 4: ...ons in these Operating Instructions is mandatory The installer must ensure that the measuring system is correctly wired in accordance with the wiring diagrams Invariably local regulations governing th...

Страница 5: ...ndicates an action or procedure which if not performed correctly can have an indirect effect on operation or trigger an unexpected response on the part of the device Explosion protected type examined...

Страница 6: ...ting instructions on CD ROM ATEX Safety Instructions for deploying a device permitted for use in hazardous areas optional Accessories eg pipe mounting kit see chapter Accessories 2 3 Certificates and...

Страница 7: ...n receipt of the goods check the following points Are the packaging or contents damaged Is anything missing from the delivery Compare the scope of delivery with the information you specified in the or...

Страница 8: ...must be present at the installation location to mount the device correctly can be found in Section Technical data These include the ambient temperature degree of protection climate class etc 3 3 Moun...

Страница 9: ...ing the field indicator on a pipe with mounting bracket steps 3 4 Mounting kit consisting of Item 1 Mounting plate Item 2 Clamps for pipe mounting Item 3 4 screws 3 4 Post installation check After ins...

Страница 10: ...cs Devices can be connected to the FOUNDATION Fieldbus in two ways Connection via conventional cable gland Chap 4 2 1 Connection via fieldbus connector optional can be purchased as an accessory Chap 4...

Страница 11: ...g plate A cable gland is supplied with the field indicator see Scope of delivery The fieldbus connector is available as an accessory a0012976 Fig 7 Mounting the cable gland or the fieldbus connector A...

Страница 12: ...land 3 Connect the cables as shown in 8 4 Retighten the cable gland and close the housing cover Terminal assignment a0011324 Fig 8 Terminal assignment ESD electrostatic discharge Protect the terminals...

Страница 13: ...he cable or the shielding In such cases the shielding of the fieldbus cable is to be grounded on only one side i e it must not be connected to the ground terminal of the housing The shield that is not...

Страница 14: ...rs offers substantial advantages over conventional wiring Field devices can be removed replaced or added at any time during normal operation Communication is not interrupted Installation and maintenan...

Страница 15: ...s of the design of the fieldbus such as distances bridged number of users electromagnetic compatibility etc Suitable fieldbus cables type A from various manufacturers for non hazardous areas are liste...

Страница 16: ...ldbus basically allows three different types of shielding Shielding at both ends Shielding at one end on the feed side with capacitance connection to the field device Shielding at one end on the feed...

Страница 17: ...minal head field housing The shield that is not connected should be insulated 4 3 6 Bus termination The start and end of each fieldbus segment are always to be terminated with a bus terminator With va...

Страница 18: ...nal checks Device condition and specifications Notes Are the indicator or the cables damaged visual check Electrical connection Notes Does the supply voltage match the specifications on the nameplate...

Страница 19: ...r the FOUNDATION Fieldbus interface using miniature switches DIP switches inside the field indicator housing 25 Switching the hardware write protection on off a0011638 Fig 12 Field indicator hardware...

Страница 20: ...value In case the status of the displayed value is Good a value equal to or above 0x80 no symbol is lit and the indicator works in normal operation If the status of the displayed value is Uncertain v...

Страница 21: ...ected in parallel to the bus line Devices requiring external power must use a separate power supply One of the most common network structures is the line structure Star tree or mixed network structure...

Страница 22: ...trast Basic Devices can only receive signals and send them to the central process control system The LAS function is deactivated in this field indicator when the unit is delivered 5 3 3 Data transfer...

Страница 23: ...n make sure that process control systems or superior configuration systems can access all device data and that the operating structure is uniform The device specific information required for this is s...

Страница 24: ...dure for commissioning the FF functions is given on 27 together with information on configuring device specific parameters System files You require the following files for commissioning and configurin...

Страница 25: ...SD electrostatic discharge Protect the terminals from electrostatic discharge Failure to observe this may result in destruction or malfunction of parts of the electronics To set the DIP switches proce...

Страница 26: ...s soon as the switch on procedure is completed Various measured values and or status values appear on the display 6 3 Commissioning Note the following points The files required for commissioning and n...

Страница 27: ...in the Display Transducer Block Display Value Settings of each channel By default the Listener Mode is activated in channel 1 The indicator will automatically display the first value of the publishin...

Страница 28: ...ctions Onsite display functions Transducer Block TB_DISP_xxxxxxxxxxx Advanced diagnostics Transducer Block TB_ADVDIAG_xxxxxxxxxx 9 Enter the desired name for the block optional For factory settings se...

Страница 29: ...or the device Detailed information on the order code in question can be obtained from your service organization When ordering accessories please specify the serial number of the device Type Order numb...

Страница 30: ...onics module defective Test with spare electronics module Order spare part Faulty connection to the fieldbus host system No connection can be made between the fieldbus host system and the indicator Ch...

Страница 31: ...s been removed the alternating time will return to its normal value written into the Parameter DISP_ALTERNATING_TIME 2 If the ALARM F437 is generated by a channel the value of that channel will be rep...

Страница 32: ...ge FF Display overflow C 561 No bargraph display symbol value will be displayed as Cause of error Value is too long to be displayed Remedy Change DISPLAY_FORMAT F 437 Device status message FF Configur...

Страница 33: ...NPT1 2 thread RIA16X GE 6 Cable gland M16x1 5 PA RAL7035 51004048 7 Small parts kit Goretex filter 2x hinge bolts cable shield ground clamp metal set 5 x bracket bolt washers RIA16X GG 8 Spare parts...

Страница 34: ...s electronic waste in the event of disposal Please pay particular attention to the local regulations governing waste disposal in your country 9 6 Software history and overview of compatibility Release...

Страница 35: ...system and activated by downloading the configuration to the device In accordance with IEC 60079 27 FISCO FNICO Breakdown information Status message as per FOUNDATION Fieldbus specification Mains volt...

Страница 36: ...ISEL The block for selecting a signal Input Selector Block ISEL allows the user to choose up to four inputs and generates an output based on the configured action Integrator INT The Integrator Block i...

Страница 37: ...lation Installation instructions Mounting location Wall or pipe mounting see Accessories Orientation No restrictions the orientation depends on the readability of the display 10 0 4 Environment Ambien...

Страница 38: ...whether the devices used in laboratories and in distributed control systems are immune to interference thus increasing their functional safety Measuring category Measuring category II as per IEC 61010...

Страница 39: ...ches in brackets A Bore for mounting directly on the wall or on optional mounting plate with 4 screws 5 mm 0 2 Weight Plastic housing approx 500 g 1 1 lb Aluminum housing approx 1 7 kg 3 75 lb Materia...

Страница 40: ...5 Parameters cannot be modified symbol Item 6 unit Item 7 Uncertain measured value status symbol Display range 9999 to 99999 Remote operation Configuration The configuration of FOUNDATION Fieldbus fun...

Страница 41: ...available upon request Other standards and guideli nes IEC 60529 Degrees of protection provided by enclosures IP code IEC 61010 1 Safety requirements for electrical equipment for measurement control...

Страница 42: ...tion tasks can be realized In addition to these blocks a field device may have other blocks e g several Input Selector function blocks if more than one process variable is available from the field dev...

Страница 43: ...on to be disabled or enabled The WRITE_LOCK parameter shows the status of the hardware write protection The following statuses are possible LOCKED The device data cannot be altered via the FOUNDATION...

Страница 44: ...M AUTO OOS The current block status appears on the display with information on pending configuration hardware or system errors including information on the alarm period date time when the error occurr...

Страница 45: ...urrent status display of the security behavior of the Analog Output and Discrete Output function blocks 17 Features FEATURES Read only Displays the additional options supported by the device Display R...

Страница 46: ...ry in kilobytes Note This parameter is not supported 21 Minimum Cycle Time MIN_CYCLE_T Read only Displays the minimum execution time 5 Block Mode MODE_BLK AUTO OOS Displays the current Actual and desi...

Страница 47: ...pecified default values as per FF Spec only FF bus parameters Restart PROCESSOR Restart Order Configuration all the parameters are reset to the original order configuration Restart PRODUCT DEFAULTS re...

Страница 48: ...ping is carried out by entering the same numerical value in the STRATEGY parameter of each individual block Factory default 0 Note This data is neither checked nor processed by the Resource Block 1 St...

Страница 49: ...the manufacturer specific parameters the hardware write protection must be deactivated see Section 5 5 39 Write Priority WRITE_PRI AUTO OOS Specifies the behavior of a write protected alarm WRITE_ALM...

Страница 50: ...trategy STRATEGY AUTO OOS Parameter for grouping and thus faster evaluation of blocks Grouping is carried out by entering the same numerical value in the STRATEGY parameter of each individual block Fa...

Страница 51: ...ation hardware or system errors including information on the alarm period date time when the error occurred Note In addition the active block alarm can be acknowledged in this parameter group The devi...

Страница 52: ...DISP_VALUE_3_DIGITAL DISP_VALUE_4_DIGITAL DISP_VALUE_5_DIGITAL DISP_VALUE_6_DIGITAL DISP_VALUE_7_DIGITAL DISP_VALUE_8_DIGITAL Read only This block shows the current digital display value The block su...

Страница 53: ...an digital type input of a function block to show its value on the display Available parameters are Off ISEL1 DISABLE_1 ISEL1 DISABLE_2 ISEL1 DISABLE_3 ISEL1 DISABLE_4 ISEL2 DISABLE_1 ISEL2 DISABLE_2...

Страница 54: ..._BLK Description Transducer Block ADVANCED DIAGNOSTIC E H parameters Parameter Index Parameter Write access with operating mode MODE_BLK Description 11 CURRENT_STATUS_ NUMBER Read only Shows the curre...

Страница 55: ...e Last diagnostics appeared 19 21 23 25 27 29 31 33 CH1_MIN_INDICATOR CH2_MIN_INDICATOR CH3_MIN_INDICATOR CH4_MIN_INDICATOR CH5_MIN_INDICATOR CH6_MIN_INDICATOR CH7_MIN_INDICATOR CH8_MIN_INDICATOR AUTO...

Страница 56: ...ed input All operations are selected by parameter and input connection The nine arithmetic functions are Flow Compensation Linear Flow Compensation Square Root Flow Compensation Approximate Btu Flow T...

Страница 57: ...19 M Manufacturer specific parameters 49 Mounting Wall 8 N Nameplate 6 Network configuration System files 24 O Opening a knock out 10 Operating mode selection 43 49 Operating modes 27 R Release 34 Res...

Страница 58: ...www endress com worldwide BA284R 09 en 02 10 71092450 FM SGML 6 0 ProMoDo...

Отзывы: