Trouble-shooting
RID16
32
Hauser
Cate
gory
No.
Status messages
– CURRENT_STATUS_
NUMBER in the
'Advanced Diagnostics'
Transducer Block
– Local display
Display symbol
Cause of error / remedy
F-
261
Device status message (FF):
Electronic board defective
F-261.
No bargraph displayed
Cause of error:
Error in the electronics.
Remedy:
Device defective, replace
F-
283
Device status message (FF):
Memory error
F-283
Display symbol
#
& No
bargraph displayed
Cause of error:
Error in memory.
Remedy:
Device defective, replace
C-
561
Device status message (FF):
Display overflow
C-561
No bargraph, display symbol
#
; value will be displayed as
"- - - - -"
Cause of error:
Value is too long to be displayed
Remedy:
Change "DISPLAY_FORMAT"
F-
437
Device status message (FF):
Configuration error
F-437
No bargraph displayed
Cause of error:
Example: Incorrect configuration; an
address in Listener Mode was entered
that is not available; a value has been
chosen for dispalying but the according
block has not been instanced
Remedy:
Check the configuration of the blocks;
the parameter
CURRENT_STATUS_MAINTENANCE
shows you which block causes the failure
C-
501
Device status message (FF):
Device preset
C-501
No bargraph, no symbol
Cause of error:
Device reset is performed.
Remedy:
Message is only displayed during reset.