Operation via FOUNDATION™ Fieldbus
RID16
48
Hauser
26
Shed Remote Cascade
(SHED_RCAS)
AUTO - OOS
Specifies the monitoring time for checking the connection between the fieldbus
host system and a function block in the RCAS operating mode.
When the monitoring time elapses, the function block changes from the RCAS
operating mode to the operating mode selected in the SHED_OPT parameter.
Factory default:
640000 1/32 ms
27
Shed Remote Out
(SHED_ROUT)
AUTO - OOS
Specifies the monitoring time for checking the connection between the fieldbus
host system and the PID function block in the ROUT operating mode.
When the monitoring time elapses, the PID function block changes from the
ROUT operating mode to the operating mode selected in the SHED_OPT
parameter (see FOUNDATION Fieldbus™ Function Blocks manual on the
supplied CD-ROM (BA062S/04)).
Factory default:
640000 1/32 ms
3
Strategy (STRATEGY)
AUTO - OOS
Parameter for grouping and thus faster evaluation of blocks. Grouping is carried
out by entering the same numerical value in the STRATEGY parameter of each
individual block.
Factory default:
0
!
Note!
This data is neither checked nor processed by the Resource Block.
1
Static Revision (ST_REV)
Read only
The revision status of the static data appears on the display.
!
Note!
The revision status is incremented on each modification of static data.
2
Tag Description
(TAG_DESC)
AUTO - OOS
Entry of a user-specific text for unique identification and assignment of the
block.
8
Test Read Write
(TEST_RW)
AUTO - OOS
!
Note!
This parameter is required only for interoperability tests and has no meaning in
normal operation.
35
Update Event
(UPDATE_EVT)
Read only
Indicates whether static block data have been altered, including date and time.
40
Write Alarm
(WRITE_ALM)
AUTO - OOS
Displays the status of the write protected alarm.
!
Note!
The alarm is triggered if the write protection is disabled.
34
Write Lock
(WRITE_LOCK)
Read only
Display status of write protection
Display:
LOCKED
Device data cannot be modified
NOT LOCKED
Device data can be modified
UNINITIALIZED
Resource Block
Parameter
Index
Parameter
Write access with
operating mode
(MODE_BLK)
Description