Proline Prowirl R 200
Installation
Hauser
15
For detailed information about inlet run correction and wet steam detection, refer
to the Special Documentation for the device on the CD-ROM provided
For the dimensions and installation lengths of the device, see the "Technical
Information" document, "Mechanical construction" section
6.1.2
Requirements from environment and process
Ambient temperature range
Compact version
Measuring device
Non-Ex:
–40 to +80 °C (–40 to +176 °F)
Ex i:
–40 to +70 °C (–40 to +158 °F)
EEx d/XP version:
–40 to +60 °C (–40 to +140 °F)
ATEX II1/2G Ex d, Ex ia:
–40 to +60 °C (–40 to +140 °F)
Local display
–20 to +60 °C (–4 to +140 °F)
1)
Additionally available as order code for "Test, certificate", option JN "Transmitter ambient temperature –
50 °C (–58 °F)".
Remote version
Transmitter
Non-Ex:
–40 to +80 °C (–40 to +176 °F)
Ex i:
–40 to +80 °C (–40 to +176 °F)
Ex d:
–40 to +60 °C (–40 to +140 °F)
ATEX II1/2G Ex d, Ex ia:
–40 to +60 °C (–40 to +140 °F)
Sensor
Non-Ex:
–40 to +85 °C (–40 to +185 °F)
Ex i:
–40 to +85 °C (–40 to +185 °F)
Ex d:
–40 to +85 °C (–40 to +185 °F)
ATEX II1/2G Ex d, Ex ia:
–40 to +85 °C (–40 to +185 °F)
Local display
–20 to +60 °C (–4 to +140 °F)
1)
Additionally available as order code for "Test, certificate", option JN "Transmitter ambient temperature –
50 °C (–58 °F)".
‣
If operating outdoors:
Avoid direct sunlight, particularly in warm climatic regions.
Temperature tables
Observe the interdependencies between the permitted ambient and fluid
temperatures when operating the device in hazardous areas.
For detailed information about the temperature tables, refer to the Technical
Information for the device on the CD-ROM provided