Proline Promag H 100
System integration
Hauser
45
the I/O electronics module to ON, restart the device and enter the default setting for the
IP address 192.168.1.212.
7. Establish the online connection to the device.
For device version with Modbus RS485 communication type
Via service interface (CDI) and "FieldCare" operating tool
1. Start FieldCare and launch the project.
2. In the network: Add a device.
The
Add device
window opens.
3. Select the
CDI Communication FXA291
option from the list and press
OK
to confirm.
4. Right-click
CDI Communication FXA291
and select the
Add device
option in the
context menu that opens.
5. Select the desired device from the list and press
OK
to confirm.
6. Establish the online connection to the device.
For details, see Operating Instructions BA00027S and BA00059S
9
System integration
For system integration: See Operating Instructions for the device on the CD-ROM
provided.
Applies only to device version with EtherNet/IP communication type
A detailed description of how to integrate the device into an automation system (e.g.
from Rockwell Automation) is available as a separate document:
Select country → Automation → Digital Communication → Feldbus device
integration → EtherNet/IP
10
Commissioning
10.1
Function check
Before commissioning the device, make sure that the post-installation and post-connection
checks have been performed.
• "Post-installation check" checklist (→ 23)