Electrical connection
Proline Promag H 100
36
Hauser
If the transmitter is used in the non-hazardous area or Zone 2/Div. 2
2 - Not used
1 - Write protection
4 - Bus termination
3 - Not used
OFF
ON
26
27
A
B
220
W
A0017610
13
Terminating resistor can be enabled via DIP switch on the main electronics module
7.4
Ensuring the degree of protection
The measuring device fulfills all the requirements for the IP66/67 degree of protection, Type
4X enclosure.
To guarantee IP66/67 degree of protection, Type 4X enclosure, carry out the following steps
after the electrical connection:
1. Check that the housing seals are clean and fitted correctly. Dry, clean or replace the
seals if necessary.
2. Tighten all housing screws and screw covers.
3. Firmly tighten the cable glands.
4. To ensure that moisture does not enter the cable entry, route the cable so that it loops
down before the cable entry ("water trap").