Proline Promag 55 PROFIBUS PA
Installation
Hauser
29
Installing the high temperature version Promag S (with PFA lining)
The high temperature version has a housing support for the thermal separation of sensor and
transmitter. The high temperature version is always used for applications in which high ambient
temperatures are encountered
in conjunction with
high fluid temperatures. The high temperature
version is obligatory if the fluid temperature e150 °C (+300 °F).
!
Note!
You will find information on permissible temperature ranges on
Insulation
Pipes generally have to be insulated if they carry very hot fluids, in order to avoid energy losses and
to prevent accidental contact with pipes at temperatures that could cause injury. Guidelines
regulating the insulation of pipes have to be taken into account.
"
Caution!
Risk of measuring electronics overheating. The housing support dissipates heat and its entire surface
area must remain uncovered. Make sure that the sensor insulation does not extend past the top of
the two sensor shells.
a0004300
Fig. 21:
Promag S (high temperature version): Insulating the pipe
Esc
E
-
+
max.