Technical data
Proline Promag 55 PROFIBUS PA
122
Hauser
SIP cleaning
Promag S:
possible with PFA (note max. temperature)
not possible with PU, PTFE, hard rubber, natural rubber
Promag H:
possible (note max. temperature)
Electromagnetic compatibility
(EMC)
According to IEC/EN 61326 and NAMUR recommendation NE 21
10.1.9
Operating conditions: Process
Medium temperature range
The permitted temperature depends on the lining of the measuring tube:
Promag S:
• 0 to +80 °C (+32 to +176 °F) for hard rubber (DN 65 to 600 / 2½ to 24")
• 0 to +60 °C (+32 to +140 °F) for natural rubber (DN 65 to 600 / 2½ to 24")
• –20 to +50 °C (–4 to +122 °F) for polyurethane (DN 25 to 600 / 1 to 24")
• –20 to +180 °C (–4 to +356 °F) for PFA (DN 25 to 200 / 1 to 8"),
restrictions
→
see diagrams
• –40 to +130 °C (–40 to +266 °F) for PTFE (DN 15 to 600 / ½ to 24"),
restrictions
→
see diagrams
a0006119-ae
Fig. 61:
Promag S compact versions (with PFA or PTFE lining)
T
A
Ambient temperature
T
F
Fluid temperature
HT
High temperature version with insulation
➀
Gray shaded area
→
temperature range from –10 to –40 °C (–14 to –40 °F) applies only to stainless steel flanges